MTD ERV 365, ERV 350 manual Menu P6  Setting additional control functions

Page 36

4

 

 

 

Values for additional control functions

Sub-menu

Description

Minimum

Maximum

Standard

P57

Setting the MTD-ERV 350 Type.

Li

Re

Li

 

Li = Left-hand version.

 

 

 

 

Re = Right-hand version.

 

 

 

Note:

The MTD-ERV 350 is set correctly at the factory.

Refer also to the identification plate for these data.

P58

Setting the fan type.

0

2

0

(Not yet avail-

0

= Standard.

 

 

 

able)

1

= Constant volume.

 

 

 

 

2

= Constant pressure.

 

 

 

Note:

The MTD-ERV 350 is set correctly at the factory.

Constantvolumeorconstantpressure fans cannot be installed subsequently.

P59

Enthalpy exchanger installed

0 (= No)

1 (= Yes) with

2 (= Yes) with-

 

 

 

moisture sen-

out moisture

 

 

 

sor

sensor

Menu P6 Setting additional control functions

 

 

 

 

 

 

 

 

 

Values for additional control functions

Sub-menu

Description

Minimum

Maximum

Standard

P60

Indicate presence of a

0 (= No)

1 (= Yes)

0

 

geothermal heat exchanger (GHE).

 

 

 

P61

Setting the percentage that the sup-

0%

99%

0%

 

ply air fan must run higher when

 

 

 

 

the valve of the geothermal heat ex-

 

 

 

 

changer (EWT) is open.

 

 

 

P62

Tghe, low

0%

15%

7%

P63

Tghe, high

10%

25%

23%

P64

Tnaheater, desired

5%

40%

18%

Menu P7 ! Read off malfunctions (and system information)

 

 

Values (malfunction) information

Sub-menu

Description

Minimum

 

Maximum

 

Standard

P70

Current software version.

Software version number

 

 

P71

Last malfunction.

Code corresponding to alarm and malfunction

 

 

display (see section 4.7)

 

 

P72

Last malfunction but one

Code corresponding to alarm and malfunction

 

 

display (see section 4.7)

 

 

P73

Last malfunction but two

Code corresponding to alarm and malfunction

 

 

display (see section 4.7)

 

 

P74

Reset a malfunction on the

0

1

0

 

MTD-ERV 350.

 

 

 

 

 

32 Instructions for the Installer

Image 36
Contents MTD-ERV 350 All rights reserved Table of Contents Checking the Scope of Supply CE Symbol Warranty and LiabilityWarranty will be voided if ForewordSafety Safety PrecautionsSafetyInstallationsandSafetyMeasures Symbols UsedDefinition of Terms Moisture Recovery Option Available Operating AidsCC Ease Operating Unit 2 3-position Switch Option Setting Date and Time Reading off the comfort temperatureBathroom Switch Option ReadingandSettingComfortTemperatureSetting the comfort temperature ReadingandSettingVentilationLevelSetting the ventilation level Reading off the ventilation levelSwitching Extractor Hood On and Off Option SwitchingSupplyandExhaustAirFansOn and OffSetting Ventilation Programme Weekday fan position Weekend fan positionAccess to the P menus Making settings in the P menusSetting Additional Functions via the P Menus Return to the main windowMenu P2 ! Set time delays Menu P1 ! Status of the functionsMenu P9 ! Status of the functions from menu P5 Use of the Switches Option Service by the UserSetting Ventilation Using 3-position Switches Setting Ventilation Using Bathroom SwitchesFor cleaning For replacementCleaning or Replacing Filters Cleaning Valves in the Home 2 3-positionSwitchwithMalfunctionLEDOn the position of the valves MalfunctionsEnd of Service Life What to Do in the Event of a Malfunction?Components of the Balanced Ventilation System Controlled Ventilation SystemMTD-ERV MTD-ERV 350 Methods of Operation Additional OptionsPreheater in MTD-ERV Ventilation via Extractor Hood Post-heater* in Duct System4 CO2 Sensor* in the Home RH Sensor* in the HomeUnderground Geothermal Heat Exchanger Technical Specifications Power supply Dimension Sketch Preconditions for Installation Installation of the MTD-ERVTransport and Unpacking Checking the Scope of SupplyWall Mounting Connection of the Air DuctsConnection of the Condensation Drain Commissioning the MTD-ERV MTD-ERV 350 RightSelect a value for the parameter with or Menu P4 ! Read off the temperatures % and ppm Menu P3 ! Set ventilation controlsMenu P5 ! Setting additional control functions Menu P6  Setting additional control functions Menu P7 ! Read off malfunctions and system informationMenu P8  Open-loop and closed-loop control ExplanationSetting the Air Specifications Maintenance by the InstallerInspection of Heat Exchanger and Fans MTD-ERV 350 L MTD-ERV 350 RFilter Cleaning, if Preheater is Fitted Malfunction Indications on the CC Ease Display Code DescriptionMalfunction indications on the CC Ease Display à Remedy Avoid contact with the PCBReset unit MIN MED T1 OK? A0 / A10 / A11 Malfunctions or Problems without Indications Problem/Malfunction Cause Check / measureSpare Parts Number PartWiring Diagram MTD-ERV 350 LEFT-HAND Standard Version Supply airWiring Diagram MTD-ERV 350 LEFT-HAND Luxury Version Supply airWiring Diagram MTD-ERV 350 RIGHT-HAND Standard Version Wiring Diagram MTD-ERV 350 RIGHT-HAND Luxury Version EC Declaration of Conformity EC Declaration of ConformityPage

ERV 350, ERV 365 specifications

The MTD ERV 365 and ERV 350 are advanced energy recovery ventilation (ERV) systems designed to enhance indoor air quality and energy efficiency in residential and commercial buildings. These units utilize cutting-edge technologies to transfer heat and moisture between incoming and outgoing air streams, optimizing the temperature and humidity levels of the conditioned air.

One of the main features of the MTD ERV 365 is its high energy recovery efficiency. Equipped with a specially designed heat exchanger, this ERV can reclaim a significant portion of the energy from the exhaust air, reducing the heating and cooling load on HVAC systems. This results in lower energy bills and decreased environmental impact. The ERV 350 offers similar benefits but is tailored for slightly smaller spaces, making it suitable for various residential applications.

Both models are constructed with durability in mind, featuring robust housing and weather-resistant materials that ensure long-lasting performance. The MTD ERV series is designed to withstand varying environmental conditions, ensuring reliable operation in challenging climates. Additionally, noise-reduction technology minimizes operational sounds, promoting a peaceful indoor environment.

User-friendly controls are another highlight of the MTD ERV systems. They come equipped with intuitive interfaces, allowing users to easily adjust settings, monitor performance, and receive maintenance notifications. Advanced sensors provide real-time data on indoor air quality parameters, ensuring optimal operation based on the specific needs of the environment.

Installation and maintenance are made straightforward with these ERV units. They feature a compact design that facilitates integration into existing HVAC systems or new constructions. Filters are easily accessible for routine cleaning or replacement, maintaining peak performance over time.

Furthermore, both the MTD ERV 365 and ERV 350 are designed with sustainability in mind. Using materials that are recyclable and energy-efficient components contributes to a reduced carbon footprint. These ERV systems also comply with various building codes and standards, ensuring they meet industry requirements for safety and efficiency.

In summary, the MTD ERV 365 and ERV 350 are sophisticated energy recovery ventilation solutions that combine advanced technologies and user-friendly features. With high energy recovery efficiency, durable construction, and easy integration, they stand out as models for improving indoor air quality and energy efficiency in a variety of settings.