CHECK GROUNDING
A common ground is required for the pilot burner, the
NOTE: If the ground circuit path is incomplete, the S86H system control will allow one
Electrical grounding connections at the pilot burner, ignitor/sensor and S86 must be clean and tight. If lead wire is damaged or deteriorated, use only No. 14 of 18 gauge,
CHECK SPARK IGNITION CIRCUIT
The electronic module and
1.Turn off the manual gas cock to prevent the flow of gas.
2.Disconnect the ignition cable at the S86 stud terminal to isolate the circuit from the pilot burner/ignitor/sensor, and prepare a short jumper lead using heavily insulated wire, such as ignition cable.
3.Energize the S86. Touch one end of the jumper firmly to the S86 ground terminal (GND). Do not disconnect the existing ground lead. Move the free end slowly toward the stud terminal to establish a spark and then pull the lead wire slowly away from the stud. Note the length of the gap at which arcing stops.
CAUTION: Do not touch either stripped end of jumper or stud terminal. This is a very high voltage circuit and electrical shock can result. Perform the test immediately upon energizing the system - before the S86H goes into safety lockout and interrupts the spark circuit.
4.An arc length of 1/8" (3.2 mm) or more indicates satisfactory voltage output. Replace the S86 if no arc can be established or the maximum gap is less than 1/8" (3.2 mm), and the fuse and power to the S86 input terminal was okay.
CONTROL MODULE FLAME SENSOR CIRCUIT
The control module provides AC power to the ignitor/sensor which the pilot burner flame rectifies to direct current. If the flame signal back to the control module is not at least 1.0 μA DC, the system will lockout. The output of the flame sensing circuit cannot be checked directly, so check the flame sensing circuit indirectly by checking the flame sensing current from the ignitor/sensor to the control module as follows:
1.Connect a meter (DC micrometer scale) in series with the flame signal ground wire (Burner Ground Terminal). Disconnect the ground wire at the control module. Connect the red (positive) lead of the meter to the free end of the ground wire. Connect the black (negative) meter lead to the
2.Restart the system and read the meter. The flame sensor current must be at least 1.0 μA, and the reading must be steady. If the reading is below the value designated or the reading is unsteady, check the pilot flame and electrical connections as described above. Also, replace the ignitor/sensor if the ceramic insulator is cracked.
EXAMPLES OF UNSATISFACTORY PILOT FLAMES
15