Specification

The minimum temperatures quoted in the specification are achieved in an ambient of 20 oC with the appropriate liquid in a well insulated

8 litre bath. However many things will affect the minimum obtainable temperature, such as: ambient temperature, insulation and length of circulation system, condition of the working liquid, heat input and so on.

DIP COOLERS

RU-200

RU-500

Minimum temperature

-20 oC

-35 oC

Cooling capacity at:

 

 

20 oC

145 W

240 W

0 oC

145 W

240 W

-10 oC

110 W

230 W

Nominal dimensions and weights

 

Overall:

 

 

Length

420 mm

430 mm

Width

235 mm

370 mm

Height

300 mm

325 mm

Coil:

 

 

Length

85 mm

85 mm

Diameter

75 mm

75 mm

Hose length to coil

1250 mm

1250 mm

Net Weight

19 kg

39 kg

FLOW COOLERS

FC-200

FC-500

Minimum temperature

-20 oC

-35 oC

Cooling capacity at:

 

 

20 oC

140 W

210 W

0 oC

140 W

210 W

-10 oC

110 W

200 W

Nominal dimensions and weights

 

Overall:

 

 

Length

420 mm

430 mm

Width

235 mm

370 mm

Height

300 mm

325 mm

Internal capacity

200 ml

200 ml

Net Weight

19 kg

39 kg

P A G E 10

Image 12
Contents RU-200,RU-500 FC-200 and FC-500 Refrigerated units Page Contents P a N D F L O W C O O L E R S U S E R ’ S M a N U a L G E P a N D F L O W C O O L E R S U S E R ’ S M a N U a L G E Operator Safety InstallationGuarantee User maintenanceAvertissement Sécurité de l’opérateurAprès utilisation GarantieEinleitung WarnungSicherheit des Anwenders Nach dem GebrauchIntroducción AvisoSeguridad del usuario InstalaciónIntroduction Dip CoolersOperator Safety Flow CoolersSpecification DIP CoolersSetting up the unit Siting ConsiderationsRecommended liquids 2345 Cleaning your unit Carrying a Dip CoolerPacking Precautionary Measures OperationOperating your unit Daily Maintenance Fault FindingService General advice General fault findingAccessories Additional Information