Dito Dean SR52, SR42, SR62 operation manual Typical Non-CE Gas Valve Typical CE Gas Valve

Page 7

SUPER RUNNER SERIES GAS FRYERS

CHAPTER 1: INSTALLATION INSTRUCTIONS

When converting from G20 (or G25) gas to G31 propane (or vice-versa), the following procedures apply:

Burner orifices and pilot orifice MUST be replaced.

Adjust orifice gas pressure to the appropriate value listed in the table on page 1-3 by turning the gas-valve adjustment screw.

After adjustment, replace the adjustment-screw cover.

Affix the new label included with the conversion kit next the existing rating plate stating that the gas type has been converted. Remove any references to the previously used gas from the existing rating plate.

When converting from G20 (20 mbar) to G25 (25 mbar), or vice-versa, or G31 (37 mbar) to G31 (50 mbar), the following procedures apply:

Check pilot-adjustment and adjust as necessary.

Other adjustments are not necessary.

Conversion from one gas family to another (i.e. changing from natural gas to propane) requires special components. Obtain the necessary components using the cross-reference in Section 1.6, Gas Conversion Components.

Conversions can only be executed by qualified, factory-authorized personnel.

NON-CE UNITS ONLY:

See gas valve illustration below and gas valve, burner and orifice location on page 1-6 when performing the following conversions.

When converting from natural gas to propane (or vice-versa), the following procedures apply:

Burner orifices and pilot orifice MUST be replaced (see page 1-6 for required component part numbers).

Adjust orifice gas pressure by turning the gas-valve adjustment screw (see page 1-3 for gas types and pressures).

After adjustment, replace the adjustment-screw cover.

Affix the new label included with the conversion kit next the existing rating plate stating that the gas type has been converted. Remove any references to the previously used gas from the existing rating plate.

Conversion from one gas family to another (i.e. changing from natural gas to propane) requires special components. Obtain the necessary components using the table on page 1-6.

Conversions can only be executed by qualified, factory-authorized personnel.

ON/PILOT/OFF

Pressure Flow

Vent tube

Knob

Adjustment

connection

 

OFF Button

 

 

Vent Tube

 

 

Connection

 

 

ON Button

 

 

(pilot gas flow)

 

 

Thermocouple

 

 

Connection

 

 

Pilot Flow

 

 

Adjustment

 

 

Pressure Tap

 

Typical Non-CE Gas Valve

 

Typical CE Gas Valve

1-5

Image 7
Contents Price $10.00 March Dean, 8700 Line Avenue, PO BoxShreveport, Louisiana Shipping Address 8700 Line AvenuePage Safety Information Super Runner Series GAS Fryers Installation InstructionsCE Units only Propane Applications Connection to the Gas Supply LineSuper Runner Series GAS Fryers Installation Instructions Typical Non-CE Gas Valve Typical CE Gas Valve Gas Conversion Components Natural Gas to Propane Kit Propane To Natural Gas KitInitial Startup Super Runner Series GAS Fryers OperationLighting the Burners Recommended Spare Parts Daily OperationHoneywell CE Wiring DiagramThis page Intentionally Left Blank Price $10.00