Trane UH-SVX01A-EN manual Motor Data P Models Voltage Selections, Amp Mca Mop Rpm

Page 38

Motor Data

Motor Data: P Models

￿CAUTION

Voltage Selections

Select appropriate AMP, MCA, and MOP for the multiple voltage motors. For example, the AMP, MCA, and MOP for Model 40 with a 230 volt Totally Enclosed motor is 1.1, 1.4, and 2.5 respectively.

Note: All motors are constant speed and operate at top speed as indicated in motor data. Models through 1/8 H.P. can be run at reduced speed with addition of optional variable speed switch. This switch is factory-calibrated for low and high speed ratings, with intermediate speeds infinitely controllable. Models 166 through 720 operate at constant speed as indicated in motor data.

Note: Stated draw is Full Load (FLA). AMP draw varies by motor manufacturer ± .2 AMPS. Verify FLA on motor data plate.

For Table 16

*Optional variable speed switch is available.

**These motors have automatic thermal over- load protection or impedance protection.

***These motors are 230/460 volts only.

Models 336 through 720 are not available for either Totally Enclosed or Explosion Proof with Overload 115/1/60 motor types.

Table 16. Standard (Totally Enclosed) Motor Type [MT=1]

Unit Model No.

AMP

MCA

MOP

HP

RPM

 

 

 

 

 

 

 

115/1/60† Operating Voltage

 

 

 

 

 

 

 

 

 

 

 

 

42

 

1.23**

1.6

2.8

1/40*

1550

 

 

 

 

 

 

 

64

 

2.1**

2.6

4.7

1/20*

1550

 

 

 

 

 

 

 

80

 

 

 

 

 

 

 

 

 

 

 

 

 

102

 

1.2**

1.5

2.7

1/8*

1070

 

 

 

 

 

 

 

122

 

 

 

 

 

 

 

 

 

 

 

 

 

146

 

2.3**

2.9

5.2

1/6

1100

 

 

166

 

 

 

 

 

 

 

 

 

 

 

 

 

202

 

3.6**

4.5

8.1

1/4

1100

 

 

 

 

 

 

 

252

 

3.6**

4.5

8.1

1/4

1100

 

 

 

 

 

 

 

280

 

5.4**

6.8

12.2

1/2

1100

 

 

 

 

 

208-230/460/3/60 Operating Voltage

 

 

 

 

 

 

 

 

 

 

 

42

 

0.98-1.1/0.55

1.2-1.4/0.7

2.2-2.5/1.2

1/6

1140

 

 

 

 

 

 

 

64

 

0.98-1.1/0.55

1.2-1.4/0.7

2.2-2.5/1.2

1/6

1140

 

 

 

 

 

 

 

80

 

 

 

 

 

 

 

 

 

 

 

 

 

102

 

0.98-1.1/0.55

1.2-1.4/0.7

2.2-2.5/1.2

1/6

1140

 

 

 

 

 

 

 

122

 

 

 

 

 

 

 

 

 

 

 

 

 

146

 

0.98-1.1/0.55 1.2-1.4/0.7

2.2-2.5/1.2

1/6

1140

 

 

166

 

 

 

 

 

 

 

 

 

 

 

 

 

202

 

1.2-1.4/0.7

1.5-1.8/0.9

2.7-3.2/1.6

1/4

1140

 

 

 

 

 

 

 

252

 

1.2-1.4/0.7

1.5-1.8/0.9

2.7-3.2/1.6

1/4

1140

 

 

 

 

 

 

 

280

 

1.8-2.0/1.0

2.3-2.5/1.3

4.1-4.5/2.3

1/2

1140

 

 

 

 

 

 

 

336

 

3.1-3.2/1.6

3.9-4.0/2.0

7.0-7.2/3.6

3/4

1140

 

 

 

 

 

 

 

384

 

 

 

 

 

 

5005.3-5.0/2.5 6.6-6.3/3.1 11.9-11.3/5.6 1-1/2 1160

7209.9-9.8/4.9 12.4-12.3/6.1 22.3-22.1/11.0 3 1165

575/3/60 Operating Voltage 42 64 80

122

0.6

0.8

1.4

1/3

1140

 

146

 

 

 

 

 

 

 

 

 

 

 

166

 

 

 

 

 

 

 

 

 

 

 

202

 

 

 

 

 

 

 

 

 

 

 

252

 

 

 

 

 

 

 

 

 

 

 

280

0.8

1.0

1.8

1/2

1140

 

 

 

 

 

 

336

1.3

1.6

2.9

3/4

1140

 

 

 

 

 

 

384

 

 

 

 

 

 

 

 

 

 

 

500

2.0

2.5

4.5

1-1/2

1160

 

 

 

 

 

 

600

 

 

 

 

 

 

 

 

 

 

 

720

3.8

4.7

8.4

3

1165

 

 

 

 

 

 

38

UH-SVX01A-EN

Image 38
Contents Unit Heaters Preface and Warnings and Cautions Hazard IdentificationContents Description Service Model Number DescriptionModel Number Description Model Number Description Digit 8-VOLTAGEThrow ft m LocationModel Maximum Mounting HT Approx. Max 300 360Location Four Point Suspension-Shelf Mounted Motors OnlyForced HOT Water Forced HOT Water High Pressure Steam LOW Pressure Steam Gravity LOW Pressure Vapor or Vacuum Lifting/Suspension Methods InstallationPeriodic Service Heavy Objects Structural Integrity17.5 InstallationUnit Size Steam Pressure PSI = Low Speed = Low output model with all air ports openModel No Maximum SpreadSteam Pressure PSI Unit Size Spread ft mDiffuser Cone See a See B Standard Low Output Model Ft mWater Temperature SteamTemperature PressurePiping Installation Installation S Type Unit Mounting Heavy ObjectsFan Guard/Louver Installation Louver Cone DiffuserVertical Unit with Louver Cone Diffuser Vertical Unit with Osha Fan GuardModels Dimensional DataDimensional Data P Model Unit Capacity MBH Fan Dia MinUnit Capacity Fan Dimensional DataModels Roughing in Dimensional Data Model Size MBHNO. NOM. FAN Dimensional Data S ModelInches DIAM. inches Ship WT. lbsHeader Type Models 18 thru Header Models NOM FAN Approx Diam ShipCorrections When Using Glycol Solution in System Technical DataTechnical Data S Models Approximate factors at varying altitudesCategory of Area Sound Rating Technical DataTechnical Data P Model Options Options S ModelsVertical Louver Cone Diffuser optional OptionsOptions P Models Electrical Connections P Model Hazardous Voltage Thermostat Wiring and LocationElectrical Connections OperationElectrical Connections Fan Motor Connections Low Voltage CCW Internal MarathonWiring Installation P Model Speed Controller with Manual Starting SwitchManual Control with Three Phase Motor Electrical Connections S Model Hazardous VoltageWiring Installation S Model Electrical Connections Standard Totally Enclosed Motor Type MT=1 Motor DataMotor Data P Models Voltage Selections AMP MCA MOP RPMUnit Model Motor DataExplosion Proof with Thermal Overload Motor Type MT=2 1145Totally Enclosed Motor Type Explosion Proof with Thermal Overload Motor TypeOutput Steam Performance DataModel S Header Type Only BTUSteam Performance Data Steam Calculations and Correction FactorsSteam Pressure in Psig kPa Properties of Saturated SteamModel P Standard Units Kg/hr Sq. mLow Output Standard Vertical Units with All Air Ports Open 037Entering Steam Pressure LBS. PER SQ. IN. Saturated AIR Temp Steam Calculations and Correction Factors P StyleSteam Correction Factors Based on 2 LBS. Steam 60 E.A.T 13.8 34.5 68.9 103.4 137.9 206.8 275.8 344.7 517.1BTU/HR Hot Water Performance DataModel S Serpentine and Header Type CFM FPMIV. Capacity AT Other Rates Hot Water Performance DataHot Water Calculations and Correction Factors S Type Water FlowHeating Capacity Factors for Various Rates of Water Flow Entering Entering Water Temperature F C AIRMinimum Water Flow TemperatType Standard Output Units CFM117.6 24.24 108.8 34.5 529 318 42.7 11,000 2250 237 1165 133 11.430 470.9 32.35 720152.2 376 138.0 041Hot Water Performance Data II. Capacity AT Other TDs HOT Water Calculations and Correction Factor P StyleCapacity @ 20 TD IV. Pressure Loss AT Other TDsMinimum Water Flow GPM 10 6 15 8 20Cleaning the Unit MaintenancePeriodic Service Hazardous Voltage Rotating ComponentsTroubleshooting Guide MaintenanceFan and Motor Assembly Additional P Model InstructionsLimited Warranty P Model Warranty InfoLimited Warranty S Model Warranty Info Page Trane

UH-SVX01A-EN specifications

The Trane UH-SVX01A-EN is an advanced unit ventilator designed to provide efficient and reliable heating, cooling, and ventilation in various commercial and educational applications. This unit is particularly engineered for use in schools, offices, and healthcare facilities, ensuring optimal indoor air quality while maintaining energy efficiency.

One of the main features of the UH-SVX01A-EN is its innovative design that incorporates cutting-edge technologies for enhanced performance. The unit is equipped with a high-efficiency fan and motor system that operates quietly while delivering consistent airflow. This ensures a comfortable environment for occupants without the disruptive noise common in traditional ventilation systems.

Another standout characteristic of the UH-SVX01A-EN is its versatility. It offers multiple configuration options, allowing it to be tailored to meet specific building requirements and occupant needs. The unit can be integrated with various control systems, including advanced building management systems, which provide precise temperature control and enhance energy savings.

The use of variable air volume technology allows the UH-SVX01A-EN to adjust airflow rates based on real-time occupancy and environmental conditions. This intelligent airflow management not only improves comfort but also significantly reduces energy consumption, aligning with sustainable building practices.

Additionally, Trane has incorporated a range of filtration options within the unit, which contribute to improved indoor air quality by capturing dust, allergens, and other airborne particulates. This makes the UH-SVX01A-EN an ideal choice for settings where air purity is paramount, such as healthcare environments.

Maintenance of the UH-SVX01A-EN is also user-friendly, with easy access to key components for servicing and inspections. Trane's commitment to reliability and efficiency is manifested in the durable materials and construction of this unit, ensuring longevity and lower lifetime operational costs.

In summary, the Trane UH-SVX01A-EN combines advanced technology, versatile configurations, and a focus on energy efficiency and indoor air quality. This unit ventilator is designed to meet the demands of modern buildings while supporting environmental sustainability initiatives. With its robust features and flexible integration options, the UH-SVX01A-EN stands out as a reliable solution for any commercial heating, cooling, and ventilation needs.