North Star M165939J owner manual Checking Generator Output

Page 32

Operation (cont’d)

4. Checking Generator Output

Although the speed of the engine was carefully adjusted at the factory so that the generator produces the proper voltage and frequency, output voltage should be checked periodically to ensure the generator is working properly before connecting loads to the generator.

WARNING:

The generator must be run at the correct speed in order to produce the proper electrical voltage and frequency. Failure to do so could result in damage to equipment powered by the generator and possible injury to the individual.

Output voltage should be checked with a portable voltage meter:

1.Start engine and allow to warm up for five minutes. Do not connect any loads.

2.Use voltage meter to check output voltage at the generator’s outlets/receptacles.

3.Measured voltage should be within the following ranges:

a.120V +/- 10% at 120V receptacles.

b.240V +/- 10% at 240V receptacles.

4.If measured voltage is not within the specified range, have generator adjusted by factory authorized personnel. Do not attempt to adjust the engine speed yourself.

NOTE:

Slight variation in voltage/speed with changing electrical loads

All engines have a tendency to slow down when a load is applied. When electrical loads are connected to the generator, the engine is more heavily loaded and as a result the speed drops slightly.

This slight decrease in speed, together with the voltage drop within the generator itself, results in a slightly lower voltage when the generator is loaded to its full capacity than when it is running with no load.

Additionally, there may be small brief surges and drops in voltage as motors connected to the generator cycle on or off.

The slight variation has no appreciable effect in the operation of motors, lights, and most appliances.

32

Image 32
Contents M165939J Hazard Signal Word Definitions Table of Contents About Your Generator About Your GeneratorAbout Your Generator cont’d Read this ManualSpecifications Specifications Item #165939JSafety Label Locations Item #165939J Part numbers DescriptionMachine Component Identification Item #165939J DescriptionReference Guide Reference 13 120V, 20A, Duplex Power Load Planning & Management Example conversion to wattsPower Load Planning & Management cont’d Total 6275WUnpacking & Delivery Inspection Installation / Initial Set-UpPlanning the Power Load Gas Hook-up Installation for Natural Gas or LPG if needed Installation / Initial Set-Up Set-up either as a Building BACK-UP or Portable Power Source Generator Current/Power Maximum Extension Cord Length Select a Suitable Site Structure allow at least a 7’ clearance Grounding the generator Battery Installation General safety rules for operation OperationOperation cont’d Operation cont’d Preparing for Operation ManualOperation cont’d Start LPG/NG supply If using Natural GasOperation cont’d Using LP/NG To start engine using LP or Natural Gas Starting the EngineTo start engine using gasoline Checking Generator Output Connecting Loads Stopping Switching Fuels during operationStop the engine using the following steps When you are finished using the generator, you must Storage & ExerciseOperation cont’d Maintenance & Repair Maintenance & RepairMaintenance & Repair cont’d Troubleshooting TroubleshootingBattery Safety Summary of Importation Information for OperationInstallation / Initial Set-up Safety Summary of Importation Information for Operation cont’dKnow how to operate \Gasoline SafetyPropane & Natural Gas Safety Personal protective equipmentSafety During Use Safety After use Generator Exploded View Rev J Fig # Description Qty Wiring Diagram Rev J Diag # Description Qty Fuel Delivery System Rev J Diag # Description QtyGenerator Head Exploded View Rev J Ref # Description Qty