North Star M165938N owner manual Checking Generator Output

Page 32

Operation (cont’d)

4. Checking Generator Output

Although the speed of the engine was carefully adjusted at the factory so that the generator produces the proper voltage and frequency, output voltage should be checked periodically to ensure the generator is working properly before connecting loads to the generator.

WARNING:

The generator must be run at the correct speed in order to produce the proper electrical voltage and frequency. Failure to do so could result in damage to equipment powered by the generator and possible injury to the individual.

Output voltage should be checked with a portable voltage meter:

1.Start engine and allow to warm up for five minutes. Do not connect any loads.

2.Use voltage meter to check output voltage at the generator’s outlets/receptacles.

3.Measured voltage should be within the following ranges:

a.120V +/- 10% at 120V receptacles.

b.240V +/- 10% at 240V receptacles.

4.If measured voltage is not within the specified range, have generator adjusted by factory authorized personnel. Do not attempt to adjust the engine speed yourself.

NOTE:

Slight variation in voltage/speed with changing electrical loads

All engines have a tendency to slow down when a load is applied. When electrical loads are connected to the generator, the engine is more heavily loaded and as a result the speed drops slightly.

This slight decrease in speed, together with the voltage drop within the generator itself, results in a slightly lower voltage when the generator is loaded to its full capacity than when it is running with no load.

Additionally, there may be small brief surges and drops in voltage as motors connected to the generator cycle on or off.

The slight variation has no appreciable effect in the operation of motors, lights, and most appliances.

32

Image 32
Contents Any Questions, Comments, Problems, or Parts Orders Watt Continuous 8,000 Watt Surge CapacityHazard Signal Word Definitions Table of Contents About Your Generator About Your GeneratorAbout Your Generator cont’d Read this ManualSpecifications Specifications Item #165938NSafety Label Locations Item #165938N Part numbers DescriptionMachine Component Identification Item #165938N DescriptionReference Guide Reference 9 Vibration Power Load Planning & Management Example conversion to wattsPower Load Planning & Management cont’d ExampleUnpacking & Delivery Inspection Installation / Initial Set-UpPlanning the Power Load Hook-up Generator Gas Hook-up Installation for Natural Gas or LPG if neededPropane LPG Installation / Initial Set-Up Set-up either as a Building BACK-UP or Portable Power Source Nema Current/Power Maximum Extension Cord Length Select a Suitable Site Outdoors onlyMonoxide exhaust Away from all air intakesStructure allow at least a 7’ clearance Grounding the generator Battery Installation General safety rules for operation OperationOperation cont’d Operation cont’d Check the oil level using the dipstick and add oil as needed Preparing for OperationGenerator on gasoline Start LPG/NG supply If using Natural GasOperation cont’d Using LP/NG To start engine using LP or Natural Gas Starting the EngineTo start engine using gasoline Checking Generator Output Connecting Loads Stopping Switching Fuels during operationStop the engine using the following steps When you are finished using the generator, you must Storage & ExerciseOperation cont’d Maintenance & Repair Maintenance & RepairMaintenance & Repair cont’d Troubleshooting TroubleshootingSummary of Important Safety Information for Operation Safety Installation & Set-upBattery Safety GeneralKnow how to operate Safety Before UseInstallation / Initial Set-up Safety Safety During Use Gasoline SafetyPropane & Natural Gas Safety Personal protective equipmentSummary of Important Safety Information for Operation cont’d Safety After use Safety Inspection/MaintenanceGenerator Exploded View Rev- N Diag # Description Qty Wiring Diagram Rev- N Generator Head Exploded View Rev- N Item # Description Qty