Page 33

INSPECTION/SETUP

BATTERY

This unit is of negative ground DO NOT connect in reverse. Always maintain battery fl uid level between the specifi ed marks. Battery life will be shortened, if the fl uid level are not properly maintained. Add only distilled water when replenishment is necessary.

DO NOT over fill. Check to see whether the battery cables are loose. Poor contact may result in poor starting or malfunctions. Always keep the terminals firmly tightened. Coating the terminals with an approved battery terminal treatment compound. Replace battery with only recommended type battery. The battery type used in this generator is BCI Group 27.

The battery is suffi ciently charged if the specifi c gravity of the battery fl uid is 1.28 (at 68° F). If the specifi c gravity should fall to 1.245 or lower, it indicates that the battery is dead and needs to be recharged or replaced.

Before charging the battery with an external electric source, be sure to disconnect the battery cables.

Battery Cable Installation

ALWAYS be sure the battery cables (Figure 34) are properly connected to the battery terminals as shown below. The red cable is connected to the positive terminal of the battery, and the black cable is connected to the negative terminal of the battery.

CAUTION

ALWAYS disconnect the negative terminal FIRST and reconnect negative terminal LAST.

Figure 34. Battery Connections

When connecting battery do the following:

1.NEVER connect the battery cables to the battery terminals when the MPEC Control Switch is in either the MANUAL position. ALWAYS make sure that the MPEC Control Switch is in the OFF/RESET position when connecting the battery.

2.Place a small amount of battery terminal treatment compound around both battery terminals. This will ensure a good connection and will help prevent corrosion around the battery terminals.

NOTICE

If the battery cable is connected incorrectly, electrical damage to the generator will occur. Pay close attention to the polarity of the battery when connecting the battery.

CAUTION

Inadequate battery connections may cause poor starting of the generator, and create other malfunctions.

ALTERNATOR

The polarity of the alternator is negative grounding type. When an inverted circuit connection takes place, the circuit will be in short circuit instantaneously resulting the alternator failure.

DO NOT put water directly on the alternator. Entry of water into the alternator can cause corrosion and damage the alternator.

WIRING

Inspect the entire generator for bad or worn electrical wiring or connections. If any wiring or connections are exposed (insulation missing) replace wiring immediately.

PIPING AND HOSE CONNECTION

Inspect all piping, oil hose, and fuel hose connections for wear and tightness. Tighten all hose clamps and check hoses for leaks.

If any hose (fuel or oil) lines are defective replace them immediately.

DCA250SSI/DCA250SSIU GENERATOR • OPERATION AND PARTS MANUAL — REV. #0 (01/12/11) — PAGE 33

Image 33 Contents
This Manual Must Accompany the Equipment AT ALL Times Model DCA250SSI Model DCA250SSIUProposition 65 Warning Nhtsa Reporting Safety DefectsDCA250SSI/DCA250SSIU 60HZ Generators Table of ContentsOrdering parts has never been easier Parts Ordering ProceduresSafety Messages Safety InformationGeneral Safety Generator Safety Always know the location of the nearest Before servicing equipment Engine SafetyTowing Safety Fuel Safety Never use fuel as a cleaning agent From fuel vapors or if fuel is spilled on a hot engineGrounding Safety Electrical SafetyPower Cord/Cable Safety Device. All installations should beEnvironmental Safety Battery SafetyDCA250SSI/DCA250SSIU SpecificationsDimensions DimensionsTypical Generator Grounding Application InstallationIndoor Installation Outdoor InstallationMounting Generator GroundingGeneral Information Item no Major ComponentsPilot Lamp Indicates the system is running Generator Control PanelOwing from the U,V, and W Output Terminal Lugs to the load Engine Operating Panel Air Filter Alarm When the air fi lterPage Output Terminal Panel Familiarization Output Terminal FamiliarizationTerminal legs O and Ground are considered bonded grounds 240V Twist-Lock Auxiliary Receptacles VAC Gfci ReceptaclesOver Current Relay Connecting LoadsSingle Phase Load Three Phase LoadLoad Application Generator Output Voltages Generator OutputsVoltage Change-Over Board Generator Amperage Maximum AmpsGenerator OUTPUTS/GAUGE Reading HOW to Read the AC Ammeter and AC Voltage GaugesAC Voltmeter Gauge Reading AC Ammeter Gauge ReadingUvwo Terminal Output Voltages Output Terminal Panel Connections3Ø-240V Uvwo Terminal Output Voltages 1Ø-240V Uvwo Terminal Output Voltages 3Ø-480V Uvwo Terminal Output Voltages 1Ø-480V Uvwo Terminal Output Voltages 1Ø-277V Uvwo Terminal Output Voltages Circuit Breakers INSPECTION/SETUPLubrication OIL Fuel CheckOnly use #2 diesel fuel when refueling Refueling ProcedureAIR Cleaner FAN Belt Tension Cleaning the RadiatorCoolant ANTIFREEZE/SUMMER COOLANT/ Water Operation in Freezing WeatherBattery Cable Installation BatteryWiring AlternatorGenerator START-UP Procedure Manual Before StartingStarting Manual Frequency Meter Starting Auto Mode Generator START-UP Procedure Auto ModeNormal Shutdown Procedure Generator SHUT-DOWN ProceduresEmergency Shutdown Procedure Never stop the engine suddenly except in an emergencyMaintenance General Inspection AIR CleanerAir Cleaner with Dust Indicator Fuel Addition Fuel Tank InspectionAIR Removal Check OIL Level Radiator CleaningReplacing Oil Filter Flushing OUT Radiator and Replacing CoolantBattery Charger and Jacket Water Heater Power Connections Trailer Maintenance Trailer MaintenanceCoupler Type of hitch used on the trailer for towing Brakes Brake AdjustmentHydraulic Surge Brakes ActuatorTIRES/WHEELS/LUG Nuts Tire Wear/InflationSuspension Never use an pneumatic air gun to tighten wheel lug nuts Lug Nut Torque RequirementsTrailer/Towing Vehicle Wiring Diagram Trailer Wiring DiagramGenerator Wiring Diagram Generator Wiring DiagramEngine Wiring Diagram Engine Wiring DiagramController Wiring Diagram Controller Wiring DiagramTroubleshooting Generator Clean/repair radiator grill Troubleshooting Engine ControllerAdjust governor actuator Adjust governor controllerMethod of Operation Troubleshooting Diagnostic LampPage Explanation of Code in Remarks Column Sample Parts ListTo 3 units Suggested Spare PartsGenerator Assy Includes Items W/# C11101008020601842334 0601823282Generator Assy C1132300114 C11544001030340406040 20A 952404470Engine Operating Panel Assy M5351100103 C33511006030019206015 0176060030Control BOX Assy 0601809667 M5214000002011808015 M7030041000QControl BOX Assy 7538070 89721777808980056310 8980137900Control BOX Assy 0027103020 06018022040601806671 0601802149Engine and Radiator Assy 1136714730 M59242000048980088400 1132402322Engine and Radiator Assy 0199900650 01999003500193602300 0605515170Output Terminal Assy M5230700003 C2231700403C0277500004 M9220100914Output Terminal Assy 0845043704 0030012000M9210000204 C2237101204Battery ASSY. DCA250SSI C9109100604 01655115513972250004 7612252004Battery ASSY. DCA250SSU M9310500404 0602220196M9104000004 0602220921Muffler Assy M5334000003 M53311000021141451920 C1334200304Fuel Tank Assy M5364000002 C13640021030605505025 0605505070Fuel Tank Assy 25A 0040010000 001011008025B 031110160 25C 021112140Enclosure Assy M5414000102 M5414000002C3414100104 M1413400004Enclosure Assy M5444200103 M54442000038225147004 M5443600004Enclosure Assy M5454100003 51B 040145008052A C1494407404 52A M5494400404Rubber Seals Assy Rubber Seal Nameplate and Decals ASSY. DCA250SSI Control BOX Group Nameplate and Decals ASSY. -DCA250SSI Battery Group Nameplate and Decals ASSY. DCA250SSIU M5550000303 Nameplate and Decals ASSY. -DCA250SSIU Decal Document BOX Located Freight Policy Terms and Conditions of Sale PartsPage HERE’S HOW to GET Help