MAINTENANCE

To restart after running out of fuel, turn the switch to the “ON” position for 15-30 seconds. Try again, if needed. This unit is equipped with an automatic air bleeding system.

CHECK OIL LEVEL

Check the crankcase oil level prior to each use, or when the fuel tank is fi lled. Insuffi cient oil may cause severe damage to the engine. Make sure the generator is level. The oil level must be between the two notches on the dipstick as shown in Figure 27.

Replacing Oil Filter

Remove the old oil fi lter.

Apply a fi lm of oil to the gasket on the new oil fi lter.

Install the new oil fi lter.

After the oil cartridge has been replaced, the engine oil will drop slightly. Run the engine for a while and check for leaks before adding more oil if needed. Clean excessive oil from engine.

FLUSHING OUT RADIATOR AND REPLACING COOLANT

Open both cocks located at the crankcase side and at the lower part of the radiator and drain coolant. Open the radiator cap while draining. Remove the overfl ow tank and drain.

Check hoses for softening and kinks. Check clamps for signs of leakage.

Tighten both cocks and replace the overfl ow tank.

Replace with coolant as recommended by the engine manufacturer.

Close radiator cap tightly.

Flush the radiator by running clean tap water through radiator until signs of rust and dirt are removed. DO NOT clean radiator core with any objects, such as a screwdriver.

WARNING

Allow engine to cool when fl ushing out radiator. Flushing the radiator while hot could cause serious burns from water or steam.

RADIATOR CLEANING

The radiator (Figure 60) should be sprayed (cleaned) with a high pressure washer when excessive amounts of dirt and debris have accumulated on the cooling fi ns or tube. When using a high pressure washer, stand at least 5 feet (1.5 meters) away from the radiator to prevent damage to the fi ns and tube.

Figure 60. Radiator Cleaning

GENERATOR STORAGE

For long term storage of the generator the following is recommended:

Drain the fuel tank completely. Treat with a fuel stabilizer if necessary.

Completely drain the oil from the crankcase and refi ll if necessary with fresh oil.

Clean the entire generator, internal and external.

Cover the generating set and store in a clean, dry place.

Disconnect the battery.

Make sure engine coolant is at proper level.

If generator is mounted on a trailer, jack trailer up and place on blocks so tires do not touch the ground or block and completely remove the tires.

JACKETWATER HEATER AND INTERNAL BATTERY CHARGER 120 VAC INPUT RECEPTACLES (OPTIONAL)

This generator can be optionally equipped with two 120 VAC, 20 amp input receptacles located on the output terminal panel.

PAGE 40 — DCA250SSI/DCA250SSIU GENERATOR • OPERATION AND PARTS MANUAL — REV. #0 (01/12/11)

Image 40
Contents Model DCA250SSI Model DCA250SSIU This Manual Must Accompany the Equipment AT ALL TimesProposition 65 Warning Reporting Safety Defects NhtsaTable of Contents DCA250SSI/DCA250SSIU 60HZ GeneratorsParts Ordering Procedures Ordering parts has never been easierSafety Information Safety MessagesGenerator Safety General Safety Always know the location of the nearest Engine Safety Before servicing equipmentFuel Safety Towing Safety Never use fuel as a cleaning agent From fuel vapors or if fuel is spilled on a hot engineElectrical Safety Grounding SafetyPower Cord/Cable Safety Device. All installations should beBattery Safety Environmental SafetySpecifications DCA250SSI/DCA250SSIUDimensions DimensionsInstallation Typical Generator Grounding ApplicationOutdoor Installation Indoor InstallationMounting Generator GroundingGeneral Information Major Components Item noGenerator Control Panel Pilot Lamp Indicates the system is runningOwing from the U,V, and W Output Terminal Lugs to the load Air Filter Alarm When the air fi lter Engine Operating PanelPage Output Terminal Familiarization Output Terminal Panel FamiliarizationTerminal legs O and Ground are considered bonded grounds VAC Gfci Receptacles 240V Twist-Lock Auxiliary ReceptaclesConnecting Loads Over Current RelayThree Phase Load Single Phase LoadLoad Application Generator Outputs Generator Output VoltagesVoltage Change-Over Board Generator Amperage Maximum AmpsHOW to Read the AC Ammeter and AC Voltage Gauges Generator OUTPUTS/GAUGE ReadingAC Voltmeter Gauge Reading AC Ammeter Gauge ReadingOutput Terminal Panel Connections Uvwo Terminal Output Voltages3Ø-240V Uvwo Terminal Output Voltages 1Ø-240V Uvwo Terminal Output Voltages1Ø-480V Uvwo Terminal Output Voltages 3Ø-480V Uvwo Terminal Output Voltages1Ø-277V Uvwo Terminal Output Voltages INSPECTION/SETUP Circuit BreakersLubrication OIL Fuel CheckRefueling Procedure Only use #2 diesel fuel when refuelingCleaning the Radiator AIR Cleaner FAN Belt TensionCoolant ANTIFREEZE/SUMMER COOLANT/ Water Operation in Freezing WeatherBattery Battery Cable InstallationWiring AlternatorBefore Starting Generator START-UP Procedure ManualStarting Manual Frequency Meter Generator START-UP Procedure Auto Mode Starting Auto ModeGenerator SHUT-DOWN Procedures Normal Shutdown ProcedureEmergency Shutdown Procedure Never stop the engine suddenly except in an emergencyGeneral Inspection AIR Cleaner MaintenanceAir Cleaner with Dust Indicator Fuel Tank Inspection Fuel AdditionAIR Removal Radiator Cleaning Check OIL LevelReplacing Oil Filter Flushing OUT Radiator and Replacing CoolantBattery Charger and Jacket Water Heater Power Connections Trailer Maintenance Trailer MaintenanceCoupler Type of hitch used on the trailer for towing Brake Adjustment BrakesHydraulic Surge Brakes ActuatorTire Wear/Inflation TIRES/WHEELS/LUG NutsSuspension Lug Nut Torque Requirements Never use an pneumatic air gun to tighten wheel lug nutsTrailer Wiring Diagram Trailer/Towing Vehicle Wiring DiagramGenerator Wiring Diagram Generator Wiring DiagramEngine Wiring Diagram Engine Wiring DiagramController Wiring Diagram Controller Wiring DiagramTroubleshooting Generator Troubleshooting Engine Controller Clean/repair radiator grillAdjust governor actuator Adjust governor controllerTroubleshooting Diagnostic Lamp Method of OperationPage Sample Parts List Explanation of Code in Remarks ColumnSuggested Spare Parts To 3 unitsGenerator Assy C1110100802 Includes Items W/#0601842334 0601823282Generator Assy C1154400103 C11323001140340406040 20A 952404470Engine Operating Panel Assy C3351100603 M53511001030019206015 0176060030Control BOX Assy M5214000002 0601809667011808015 M7030041000QControl BOX Assy 8972177780 75380708980056310 8980137900Control BOX Assy 0601802204 00271030200601806671 0601802149Engine and Radiator Assy M5924200004 11367147308980088400 1132402322Engine and Radiator Assy 0199900350 01999006500193602300 0605515170Output Terminal Assy C2231700403 M5230700003C0277500004 M9220100914Output Terminal Assy 0030012000 0845043704M9210000204 C2237101204Battery ASSY. DCA250SSI 0165511551 C91091006043972250004 7612252004Battery ASSY. DCA250SSU 0602220196 M9310500404M9104000004 0602220921Muffler Assy M5331100002 M53340000031141451920 C1334200304Fuel Tank Assy C1364002103 M53640000020605505025 0605505070Fuel Tank Assy 0010110080 25A 004001000025B 031110160 25C 021112140Enclosure Assy M5414000002 M5414000102C3414100104 M1413400004Enclosure Assy M5444200003 M54442001038225147004 M5443600004Enclosure Assy 51B 0401450080 M545410000352A C1494407404 52A M5494400404Rubber Seals Assy Rubber Seal Nameplate and Decals ASSY. DCA250SSI Control BOX Group Nameplate and Decals ASSY. -DCA250SSI Battery Group Nameplate and Decals ASSY. DCA250SSIU M5550000303 Nameplate and Decals ASSY. -DCA250SSIU Decal Document BOX Located Terms and Conditions of Sale Parts Freight PolicyPage HERE’S HOW to GET Help
Related manuals
Manual 4 pages 50.99 Kb

DCA250SSIU, DCA250SSI specifications

The Multiquip DCA250SSI and DCA250SSIU are powerful diesel generators designed to meet the demanding energy needs of various industries. These models are specifically engineered for reliability, efficiency, and performance, making them suitable for commercial applications, construction sites, and emergency backup power.

One of the standout features of both the DCA250SSI and DCA250SSIU is their impressive power output. Each model is capable of delivering 250 kVA, allowing users to run multiple equipment and tools simultaneously without worrying about power shortages. This makes them ideal for large-scale operations where consistent power is critical.

Both generators are equipped with a robust industrial-grade engine, ensuring long-lasting performance and durability. The DCA250SSI features a Kohler 4038T, whereas the DCA250SSIU includes a Yanmar engine. These engines are designed to operate efficiently under heavy loads while minimizing fuel consumption. The advanced design helps reduce emissions, making these models environmentally friendly.

The DCA250SSI and DCA250SSIU come with a sound-attenuated enclosure, which significantly reduces noise levels during operation. This design makes them suitable for use in urban settings or noise-sensitive environments, allowing businesses to comply with regulations without compromising on power supply.

Furthermore, both models integrate advanced technologies to enhance user experience. The digital controller allows for easy monitoring and control of the generator's performance, providing crucial information such as voltage, frequency, and engine parameters in real-time. This feature helps operators stay informed of the system's status and facilitates timely maintenance when needed.

Safety is another critical consideration in the design of these generators. The DCA250SSI and DCA250SSIU include a comprehensive range of safety features, such as low oil pressure shutdown, high-temperature shutdown, and overcurrent protection, ensuring reliable operation while safeguarding against potential hazards.

Versatility is key with these models. They can be configured for both single-phase and three-phase output, catering to diverse energy requirements across different applications. Additionally, their compact design makes them easy to transport and install, further enhancing their appeal for rental companies and on-the-go operations.

In conclusion, the Multiquip DCA250SSI and DCA250SSIU stand out in the generator market with their blend of power output, fuel efficiency, noise reduction, and advanced technologies. Their robust design and safety features make them a reliable choice for a wide array of industries, offering peace of mind and consistent energy wherever it's needed.