Multiquip dca25ssiu3 manual Load Application, Single Phase Load, Three Phase Load, Type of Load

Page 23

Load Application

Single Phase Load

Always be sure to check the nameplate on the generator and equipment to insure the wattage, amperage, frequency, and voltage requirements are satisfactorily supplied by the generator for operating the equipment.

Generally, the wattage listed on the nameplate of the equipment is its rated output. Equipment may require 130—150% more wattage than the rating on the nameplate, as the wattage is influenced by the efficiency, power factor and starting system of the equipment.

NOTICE

If wattage is not given on the equipment’s name plate, approximate wattage may be determined by multiplying nameplate voltage by the nameplate amperage.

WATTS = VOLTAGE x AMPERAGE

The power factor of this generator is 0.8. SeeTable 5 below when connecting loads.

Table 5. Power Factor By Load

 

Type of Load

 

 

Power Factor

Single-phase induction motors

 

 

0.4-0.75

 

 

 

 

Electric heaters, incandescent lamps

 

1.0

 

Fluorescent lamps, mercury lamps

 

0.4-0.9

Electronic devices, communication

 

1.0

 

equipment

 

 

 

 

 

 

 

 

 

 

 

 

Common power tools

 

 

 

0.8

 

 

 

 

 

 

 

 

 

 

Table 6. Cable Selection (60 Hz, Single Phase Operation)

 

 

 

 

 

 

 

 

Current

Load in Watts

Maximum Allowable Cable Length

 

 

 

 

 

 

 

 

in

At 100

At 200

#10 Wire

#12 Wire

#14 Wire

 

#16 Wire

Amperes

 

Volts

Volts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.5

300

600

1000 ft.

600 ft.

375 ft.

 

250 ft.

 

 

 

 

 

 

 

 

 

5

600

1200

500 ft.

300 ft.

200 ft.

 

125 ft.

 

 

 

 

 

 

 

 

 

7.5

900

1800

350 ft.

200 ft.

125 ft.

 

100 ft.

 

 

 

 

 

 

 

 

 

10

1200

2400

250 ft.

150 ft.

100 ft.

 

 

 

 

 

 

 

 

 

 

 

15

1800

3600

150 ft.

100 ft.

65 ft.

 

 

 

 

 

 

 

 

 

 

 

20

2400

4800

125 ft.

75 ft.

50 ft.

 

 

 

 

 

 

 

 

 

 

 

 

CAUTION: Equipment damage can result from low voltage

 

 

 

 

 

 

 

 

 

 

Three Phase Load

When calculating the power requirements for 3-phase power use the following equation:

NOTICE

If 3Ø load (kVA) is not given on the equipment nameplate, approximate 3Ø load may be determined by multiplying voltage by amperage by 1.732.

NOTICE

Motors and motor-driven equipment draw much greater current for starting than during operation.

An inadequate size connecting cable which cannot carry the required load can cause a voltage drop which can burn out the appliance or tool and overheat the cable. See Table 6.

„„When connecting a resistance load such as an incandescent lamp or electric heater, a capacity of up to the generating set’s rated output (kW) can be used.

„„When connecting a fluorescent or mercury lamp, a capacity of up to the generating set’s rated output (kW) multiplied by 0.6 can be used.

„„When connecting an electric drill or other power tools, pay close attention to the required starting current capacity.

When connecting ordinary power tools, a capacity of up to the generating set’s rated output (kW) multiplied by 0.8 can be used.

DANGER

Before connecting this generator to any building’s electrical system, a licensed electrician must install an isolation (transfer) switch. Serious damage to the building’s electrical system may occur without this transfer switch.

DCA25SSIU3 (with MLT25 series) • operation and parts manual — rev. #1 (01/24/13) — page 23

Image 23
Contents Model dca25ssiu3 Parts List NO. M1870301004CProposition 65 warning Administrator Reporting Safety DefectsDCA25SSIU3 Generator Table of ContentsChoose from three easy options SaFeTY SYMBoLS Safety InformationSaFeTY MeSSageS GeneraTor SaFeTY GeneraL SaFeTYIf operating in speed ranges above the maximum allowable EngIne SaFeTYRestricted. If the air fl ow is From fuel vapors or if fuel is spilled on a hot engine FUeL SaFeTYTowIng SaFeTY „ never use fuel as a cleaning agentDeath ELeCTrICaL SaFeTYGrounding Safety Power Cord/Cable SafetyEnvIronMenTaL SaFeTY BaTTerY SaFeTYModel Isuzu BV 4LE2 Tier Specifications240/120 Dimensions DimensionsTypical Generator Grounding Application InstallationGenerator Grounding Outdoor InstallationIndoor Installation MountingGeneral Information Item no Major ComponentsGenerator Control Panel Generator Control PanelEngine Operating Panel Output Terminal Panel is provided with the following Output Terminal FamiliarizationTerminal legs O and Ground are considered bonded grounds VAC Gfci Receptacles Removing the Plastic Face Plate Hard Wire Hookup PanelOver Current Relay Connecting LoadsType of Load Single Phase LoadThree Phase Load Load ApplicationGenerator Amperage Voltage Selector SwitchVoltage Selector Switch Locking Button Generator Output VoltagesAC Ammeter Gauge Reading How to Read the ac ammeter and ac voltage gaugesGenerator OUTPUTS/gauge reading AC Voltmeter Gauge Reading3Ø-208V/1Ø-120V Uvwo Terminal Output Voltages Uvwo Terminal Output Voltages3Ø-240/139 Uvwo Terminal Output Voltages 1Ø-240/120V Uvwo Terminal Output Voltages 3Ø-480/277V Uvwo Terminal Output VoltagesFuel Check Inspection/SETUPCircuit Breakers Lubrication OilRemove fuel cap from filler neck and fill tank Figure Refueling ProcedureOnly use #2 diesel fuel when refueling Coolant Antifreeze/Summer Coolant/ WaterOperation in Freezing Weather Cleaning the RadiatorAir Cleaner Fan Belt Tension BatteryAlternator Battery Cable InstallationWiring When connecting battery do the followingEngine’s exhaust contains harmful emissions Before StartingStarting Starting ManualIgnition Switch Start Position Automatic Shut-down System Light tower operation Normal Shutdown ProcedureEmergency Shutdown Procedure Air Cleaner with Dust Indicator MaintenanceGeneral Inspection Air Cleaner Fuel Tank Inspection Cleaning Inside the Fuel TankFuel Addition Removing Water from the Fuel TankFlushing Out Radiator and Replacing Coolant Radiator CleaningCheck Oil Level Replacing Oil FilterGenerator Wiring Diagram Generator Wiring DiagramEngine Wiring Diagram Engine Wiring DiagramSymptom Possible Problem Solution Troubleshooting GeneratorPage Explanation of Code in Remarks Column Qty Description Suggested Spare PartsTo 3 units Generator Assy 8001070003 B11102006027961025004 0601822630Control box Assy 0601842384 M12130011020601870430 0021004075Control box Assy 0601801041 06018076410601808985 AC AMMETER, 0~50A/100A5A 0601801040 0601806859Engine and Radiator Assy M1303200304 M19232001048972606490 2944566410Engine and Radiator Assy 0199900600 M92002000040150000018 0016906020Output Terminal Assy 0039308000 M1230700003M9220000004 M9220000104Battery Assy 0602220920 0602220185B9310500014 M9103000304Muffler Assy M1333200014 M1330100803M1333002803 8970420280Fuel Filter Assy 8970398340 894367292214A 8980374810 M1366700104Enclosure Assy M1493104903 M1413003302M1413400004 M1423002302Enclosure Assy Part Name QTY Rubber Seals Assy REMArks Nameplate and Decals Assy M1550003412 M1550000104M1550000204 M1550003312Freight Policy Terms and Conditions of Sale PartsPage HERE’S HOW to GET Help

dca25ssiu3 specifications

The Multiquip DCA25SSIU3 is a powerful and reliable generator that exemplifies performance and efficiency in portable power solutions. As part of Multiquip’s DCA series, this generator is designed with a focus on providing optimal power for construction sites, events, emergency backup, and various industrial applications.

One of the key features of the DCA25SSIU3 is its robust 25 kVA output, which is capable of handling significant loads with ease. This makes it suitable for powering multiple tools and equipment simultaneously, ensuring that operators can complete their tasks without interruption. The generator is equipped with a durable and quiet-running engine, which contributes to its reputation for reliability and ease of use.

In terms of technological advancements, the DCA25SSIU3 incorporates advanced inverter technology. This feature ensures that the output power is stable and clean, making it ideal for sensitive electronic equipment. This technology not only enhances performance but also increases fuel efficiency, allowing for longer operational periods between refueling.

Another notable characteristic of the DCA25SSIU3 is its compact design, coupled with a user-friendly control panel. The generator is designed to be portable, with integrated lifting points that make it easy to transport across various job sites. The control panel features clear indicators for easy monitoring of power output, fuel level, and operational status, empowering users to operate the generator with confidence.

Moreover, the DCA25SSIU3 is built with durability in mind. It features a rugged enclosure that protects vital components from the elements, including rain, dust, and debris. This design ensures that the generator can withstand tough job site conditions while providing reliable power.

In terms of safety, the DCA25SSIU3 is engineered with multiple protective features, including low oil shutdown and overload protection, which helps to prevent damage to the generator and connected equipment.

Overall, the Multiquip DCA25SSIU3 stands out as a robust, efficient, and reliable choice for those seeking a dependable portable power solution that meets the demands of various environments and applications.