GENERATOR START-UP PROCEDURE

3.Turn the ignition key to the start position (Figure 40). Once the engine starts, release the ignition key and allow it to return to the RUN position (Figure 38).

If the engine fails to start after 10 seconds, wait approximately 30 seconds and repeat steps 3-4.

8.The ammeter (Figure 44) will indicate zero amps with no load applied. When a load is applied, the ammeter will indicate the amount of current that the load is drawing from the generator.

Figure 40. Ignition Switch (Start Position)

4.Let the engine run for 1-2 minutes. Listen for any abnormal noises. If any abnormalities exist, shut down the engine and correct the problem.

5.The generator’s frequency meter (Figure 41) should be displaying the 60 cycle output frequency in HERTZ.

Figure 41. Frequency Meter

6.The generator’s AC-voltmeter(Figure 42) will display the generator’s output in VOLTS..

Figure 42. Voltmeter Meter

7.If the voltage is not within the specified tolerance use the voltage adjustment control knob (Figure 43) to increase or decrease the desired voltage.

Figure 43. Voltage Adjust Control Knob

Figure 44. Ammeter (No Load)

9.The engine oil pressure gauge (Figure 45) will indicate the oil pressure of the engine. Under normal operating conditions the oil pressure is approximately 28 to 71 psi. (193~490 kPa).

Figure 45. Oil Pressure Gauge

10.The coolant temperature gauge (Figure 46) will indicate the coolant temperature. Under normal operating conditions the coolant temperature should be between 165°~203°F (74°~95°C) (Green Zone).

Figure 46. Coolant Temperature Gauge

11.The tachometer gauge (Figure 47) will indicate the speed of the engine when the generator is operating. Under normal operating conditions this speed is approximately 1800 RPM’s.

Figure 47. Engine Tachometer Gauge

DCA25SSIU3 (with MLT25 series) • operation and parts manual — rev. #1 (01/24/13) — page 33

Image 33
Contents Model dca25ssiu3 Parts List NO. M1870301004CProposition 65 warning Administrator Reporting Safety DefectsDCA25SSIU3 Generator Table of ContentsChoose from three easy options Safety Information SaFeTY MeSSageSSaFeTY SYMBoLS GeneraTor SaFeTY GeneraL SaFeTYEngIne SaFeTY Restricted. If the air fl ow isIf operating in speed ranges above the maximum allowable TowIng SaFeTY FUeL SaFeTY„ never use fuel as a cleaning agent From fuel vapors or if fuel is spilled on a hot engineGrounding Safety ELeCTrICaL SaFeTYPower Cord/Cable Safety DeathEnvIronMenTaL SaFeTY BaTTerY SaFeTYSpecifications 240/120Model Isuzu BV 4LE2 Tier Dimensions DimensionsTypical Generator Grounding Application InstallationIndoor Installation Outdoor InstallationMounting Generator GroundingGeneral Information Item no Major ComponentsGenerator Control Panel Generator Control PanelEngine Operating Panel Output Terminal Familiarization Terminal legs O and Ground are considered bonded groundsOutput Terminal Panel is provided with the following VAC Gfci Receptacles Removing the Plastic Face Plate Hard Wire Hookup PanelOver Current Relay Connecting LoadsThree Phase Load Single Phase LoadLoad Application Type of LoadVoltage Selector Switch Locking Button Voltage Selector SwitchGenerator Output Voltages Generator AmperageGenerator OUTPUTS/gauge reading How to Read the ac ammeter and ac voltage gaugesAC Voltmeter Gauge Reading AC Ammeter Gauge ReadingUvwo Terminal Output Voltages 3Ø-240/139 Uvwo Terminal Output Voltages3Ø-208V/1Ø-120V Uvwo Terminal Output Voltages 1Ø-240/120V Uvwo Terminal Output Voltages 3Ø-480/277V Uvwo Terminal Output VoltagesCircuit Breakers Inspection/SETUPLubrication Oil Fuel CheckOnly use #2 diesel fuel when refueling Refueling ProcedureCoolant Antifreeze/Summer Coolant/ Water Remove fuel cap from filler neck and fill tank FigureAir Cleaner Fan Belt Tension Cleaning the RadiatorBattery Operation in Freezing WeatherWiring Battery Cable InstallationWhen connecting battery do the following AlternatorStarting Before StartingStarting Manual Engine’s exhaust contains harmful emissionsIgnition Switch Start Position Light tower operation Normal Shutdown Procedure Emergency Shutdown ProcedureAutomatic Shut-down System Maintenance General Inspection Air CleanerAir Cleaner with Dust Indicator Fuel Addition Cleaning Inside the Fuel TankRemoving Water from the Fuel Tank Fuel Tank InspectionCheck Oil Level Radiator CleaningReplacing Oil Filter Flushing Out Radiator and Replacing CoolantGenerator Wiring Diagram Generator Wiring DiagramEngine Wiring Diagram Engine Wiring DiagramSymptom Possible Problem Solution Troubleshooting GeneratorPage Explanation of Code in Remarks Column Suggested Spare Parts To 3 unitsQty Description Generator Assy 7961025004 B11102006020601822630 8001070003Control box Assy 0601870430 M12130011020021004075 0601842384Control box Assy 0601808985 AC AMMETER, 0~50A/100A5A 0601801040 06018076410601806859 0601801041Engine and Radiator Assy 8972606490 M19232001042944566410 M1303200304Engine and Radiator Assy 0150000018 M92002000040016906020 0199900600Output Terminal Assy M9220000004 M1230700003M9220000104 0039308000Battery Assy B9310500014 0602220185M9103000304 0602220920Muffler Assy M1333002803 M13301008038970420280 M1333200014Fuel Filter Assy 14A 8980374810 8943672922M1366700104 8970398340Enclosure Assy M1413400004 M1413003302M1423002302 M1493104903Enclosure Assy Part Name QTY Rubber Seals Assy REMArks Nameplate and Decals Assy M1550000204 M1550000104M1550003312 M1550003412Freight Policy Terms and Conditions of Sale PartsPage HERE’S HOW to GET Help

dca25ssiu3 specifications

The Multiquip DCA25SSIU3 is a powerful and reliable generator that exemplifies performance and efficiency in portable power solutions. As part of Multiquip’s DCA series, this generator is designed with a focus on providing optimal power for construction sites, events, emergency backup, and various industrial applications.

One of the key features of the DCA25SSIU3 is its robust 25 kVA output, which is capable of handling significant loads with ease. This makes it suitable for powering multiple tools and equipment simultaneously, ensuring that operators can complete their tasks without interruption. The generator is equipped with a durable and quiet-running engine, which contributes to its reputation for reliability and ease of use.

In terms of technological advancements, the DCA25SSIU3 incorporates advanced inverter technology. This feature ensures that the output power is stable and clean, making it ideal for sensitive electronic equipment. This technology not only enhances performance but also increases fuel efficiency, allowing for longer operational periods between refueling.

Another notable characteristic of the DCA25SSIU3 is its compact design, coupled with a user-friendly control panel. The generator is designed to be portable, with integrated lifting points that make it easy to transport across various job sites. The control panel features clear indicators for easy monitoring of power output, fuel level, and operational status, empowering users to operate the generator with confidence.

Moreover, the DCA25SSIU3 is built with durability in mind. It features a rugged enclosure that protects vital components from the elements, including rain, dust, and debris. This design ensures that the generator can withstand tough job site conditions while providing reliable power.

In terms of safety, the DCA25SSIU3 is engineered with multiple protective features, including low oil shutdown and overload protection, which helps to prevent damage to the generator and connected equipment.

Overall, the Multiquip DCA25SSIU3 stands out as a robust, efficient, and reliable choice for those seeking a dependable portable power solution that meets the demands of various environments and applications.