Multiquip dca25ssiu3 manual Generator Output Voltages, Voltage Selector Switch, Generator Amperage

Page 24

GENERATOR OUTPUTS

Generator Output Voltages

A wide range of voltages are available to supply voltage for many different applications.Voltages are selected by using the voltage selector switch (Figure 13). To obtain some of the voltages as listed in Table 7 (see below) will require a fine adjustment using the voltage regulator (VR) control knob located on the control panel.

Voltage Selector Switch

The voltage selector switch (Figure 13) is located above the output terminal panel’s Hard Wire Hook-up Panel. It has been provided for ease of voltage selection.

Generator Amperage

Table 8 shows the maximum amps the generator can provide. DO NOT exceed the maximum amps as listed..

Table 8. Generator Maximum Amps

Rated Voltage

Maximum Amps

 

 

1Ø 120 Volt

55.6 amps (4 wire)

60A x 2 (Zigzag)

 

1Ø 240 Volt

27.8 amps (4 wire)

60A (Zigzag)

 

3Ø 240 Volt

60 amps

 

 

3Ø 480 Volt

30 amps

 

 

Figure 13. Voltage Selector Switch

Voltage Selector Switch Locking Button

To lock the voltage selector switch, press and hold the red button located at the bottom of the switch. While holding the red button down, insert a pad lock into the hole next to the button to retain it in the inward locked position. When the lock is removed, the red button is spring loaded and will return to its normal outward unlocked position.

CAUTION

NEVER change the position of the voltage selector switch while the engine is running. ALWAYS place circuit breaker in the OFF position before selecting voltage.

Table 7. Voltages Available

UVWO Output

Voltage Selector Switch

Voltage Selector Switch

Terminal Lugs

3-Phase 240/139V Position

3-Phase 480/277V Position

 

 

 

 

 

 

 

Line-Line

208V

220V

240V

416V

440V

480V

 

 

 

 

 

 

 

Line-Neutral

120V

127V

139V

240V

254V

277V

 

 

 

 

 

 

 

Voltage Selector Switch Single-Phase 240/120V Position

 

 

 

 

 

 

 

 

Line-Neutral/

120V

N/A

N/A

240V

N/A

N/A

Line-Line

Line-Neutral

Line-Line

 

 

 

 

 

 

 

 

 

 

 

GFCI Receptacle Load Capability

The load capability of the GFCI receptacles is directly related to the voltage being supplied at either the output terminals or the 2 twist lock auxiliary receptacles.

Table 9 and Table 10 show what amount of current is available at the GFCI receptacles when the output terminals and twist lock receptacles are in use. Be careful that your load does not to exceed the available current capability at the receptacles.

Table 9. 1Ø GFCI Receptacle Load Capacity

KW in Use

Available Load

Twist Lock (C6369)

Current (Amps)

1Ø 240/120V

GFCI Duplex

5-20R 120V

 

14.4

0

13.2

5 amps/receptacle

12.0

10 amps/receptacle

 

 

10.8

15 amps/receptacle

 

 

9.6

20 amps/receptacle

 

 

Table 10. 3Ø Generator Maximum Amps

KVA in Use

Available Load

(UVWO Terminals)

Current (Amps)

3Ø 240/480V

GFCI Duplex

5-20R 120V

 

25

0 amps/receptacle

 

 

20.8

5 amps/receptacle

 

 

16.7

10 amps/receptacle

 

 

12.5

15 amps/receptacle

 

 

8.4

20 amps/receptacle

 

 

page 24 — DCA25SSIU3 (with MLT25 series) • operation and parts manual — rev. #1 (01/24/13)

Image 24
Contents Parts List NO. M1870301004C Model dca25ssiu3Proposition 65 warning Reporting Safety Defects AdministratorTable of Contents DCA25SSIU3 GeneratorChoose from three easy options Safety Information SaFeTY MeSSageSSaFeTY SYMBoLS GeneraL SaFeTY GeneraTor SaFeTYEngIne SaFeTY Restricted. If the air fl ow isIf operating in speed ranges above the maximum allowable FUeL SaFeTY TowIng SaFeTY„ never use fuel as a cleaning agent From fuel vapors or if fuel is spilled on a hot engineELeCTrICaL SaFeTY Grounding SafetyPower Cord/Cable Safety DeathBaTTerY SaFeTY EnvIronMenTaL SaFeTYSpecifications 240/120Model Isuzu BV 4LE2 Tier Dimensions DimensionsInstallation Typical Generator Grounding ApplicationOutdoor Installation Indoor InstallationMounting Generator GroundingGeneral Information Major Components Item noGenerator Control Panel Generator Control PanelEngine Operating Panel Output Terminal Familiarization Terminal legs O and Ground are considered bonded groundsOutput Terminal Panel is provided with the following Removing the Plastic Face Plate Hard Wire Hookup Panel VAC Gfci ReceptaclesConnecting Loads Over Current RelaySingle Phase Load Three Phase LoadLoad Application Type of LoadVoltage Selector Switch Voltage Selector Switch Locking ButtonGenerator Output Voltages Generator AmperageHow to Read the ac ammeter and ac voltage gauges Generator OUTPUTS/gauge readingAC Voltmeter Gauge Reading AC Ammeter Gauge ReadingUvwo Terminal Output Voltages 3Ø-240/139 Uvwo Terminal Output Voltages3Ø-208V/1Ø-120V Uvwo Terminal Output Voltages 3Ø-480/277V Uvwo Terminal Output Voltages 1Ø-240/120V Uvwo Terminal Output VoltagesInspection/SETUP Circuit BreakersLubrication Oil Fuel CheckRefueling Procedure Only use #2 diesel fuel when refuelingCoolant Antifreeze/Summer Coolant/ Water Remove fuel cap from filler neck and fill tank FigureCleaning the Radiator Air Cleaner Fan Belt TensionBattery Operation in Freezing WeatherBattery Cable Installation WiringWhen connecting battery do the following AlternatorBefore Starting StartingStarting Manual Engine’s exhaust contains harmful emissionsIgnition Switch Start Position Light tower operation Normal Shutdown Procedure Emergency Shutdown ProcedureAutomatic Shut-down System Maintenance General Inspection Air CleanerAir Cleaner with Dust Indicator Cleaning Inside the Fuel Tank Fuel AdditionRemoving Water from the Fuel Tank Fuel Tank InspectionRadiator Cleaning Check Oil LevelReplacing Oil Filter Flushing Out Radiator and Replacing CoolantGenerator Wiring Diagram Generator Wiring DiagramEngine Wiring Diagram Engine Wiring DiagramTroubleshooting Generator Symptom Possible Problem SolutionPage Explanation of Code in Remarks Column Suggested Spare Parts To 3 unitsQty Description Generator Assy B1110200602 79610250040601822630 8001070003Control box Assy M1213001102 06018704300021004075 0601842384Control box Assy 0601807641 0601808985 AC AMMETER, 0~50A/100A5A 06018010400601806859 0601801041Engine and Radiator Assy M1923200104 89726064902944566410 M1303200304Engine and Radiator Assy M9200200004 01500000180016906020 0199900600Output Terminal Assy M1230700003 M9220000004M9220000104 0039308000Battery Assy 0602220185 B9310500014M9103000304 0602220920Muffler Assy M1330100803 M13330028038970420280 M1333200014Fuel Filter Assy 8943672922 14A 8980374810M1366700104 8970398340Enclosure Assy M1413003302 M1413400004M1423002302 M1493104903Enclosure Assy Part Name QTY Rubber Seals Assy REMArks Nameplate and Decals Assy M1550000104 M1550000204M1550003312 M1550003412Terms and Conditions of Sale Parts Freight PolicyPage HERE’S HOW to GET Help

dca25ssiu3 specifications

The Multiquip DCA25SSIU3 is a powerful and reliable generator that exemplifies performance and efficiency in portable power solutions. As part of Multiquip’s DCA series, this generator is designed with a focus on providing optimal power for construction sites, events, emergency backup, and various industrial applications.

One of the key features of the DCA25SSIU3 is its robust 25 kVA output, which is capable of handling significant loads with ease. This makes it suitable for powering multiple tools and equipment simultaneously, ensuring that operators can complete their tasks without interruption. The generator is equipped with a durable and quiet-running engine, which contributes to its reputation for reliability and ease of use.

In terms of technological advancements, the DCA25SSIU3 incorporates advanced inverter technology. This feature ensures that the output power is stable and clean, making it ideal for sensitive electronic equipment. This technology not only enhances performance but also increases fuel efficiency, allowing for longer operational periods between refueling.

Another notable characteristic of the DCA25SSIU3 is its compact design, coupled with a user-friendly control panel. The generator is designed to be portable, with integrated lifting points that make it easy to transport across various job sites. The control panel features clear indicators for easy monitoring of power output, fuel level, and operational status, empowering users to operate the generator with confidence.

Moreover, the DCA25SSIU3 is built with durability in mind. It features a rugged enclosure that protects vital components from the elements, including rain, dust, and debris. This design ensures that the generator can withstand tough job site conditions while providing reliable power.

In terms of safety, the DCA25SSIU3 is engineered with multiple protective features, including low oil shutdown and overload protection, which helps to prevent damage to the generator and connected equipment.

Overall, the Multiquip DCA25SSIU3 stands out as a robust, efficient, and reliable choice for those seeking a dependable portable power solution that meets the demands of various environments and applications.