LSI DF1153-E1 manual Environmental Requirements

Page 25

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Environmental Requirements

Environmental Requirements

Table 8 Drive Module and E2400 Command Module Environmental Requirements

Element

Unit of Measure

E3300 and FC-1 10x

FC-1 14x and E2400 14x

Requirement

Requirement

 

 

 

 

 

 

 

Optimum

22º C (72º F)

22º C (72º F)

 

Operating Range

10º C to 40º C (50º F to 104º F)

10º C to 40º C (50º F to 104º F)

Temperature

Storage Range

-10ºC to 50º C (14º F to 120º F)

-10ºC to 50º C (14º F to 120º F)

 

Transit Range

-40ºC to 60º

-40ºC to 60º C

 

(-40ºF to 140º F)

(-40ºF to 140º F)

 

 

Temperature

Operating Range

10º C (18º F) per hour

10º C (18º F) per hour

 

15º C (27º F) per hour

15º C (27º F) per hour

Change

Storage Range

(Max. Allowed)

 

 

 

Transit Range

20º C (36º F) per hour

20º C (36º F) per hour

 

 

Operating Range

20% to 80%

20% to 80%

 

 

 

 

 

Storage Range

10% to 90%

10% to 90%

Relative Humidity

 

 

 

Transit Range

5% to 95%

5% to 95%

(No Condensation)

 

 

 

 

Max. Dew Point

26º C (79º F)

26º C (79º F)

 

Max. Gradient

10% per hour

10% per hour

 

 

 

 

Sound

Sound Power

6.0 bels

6.0 bels

 

 

 

Sound Pressure

60 dBA

60 dBA

 

 

 

 

 

 

Operating Range

30.5 m (100 ft.) below sea level

 

3000 m (9840 ft.) above sea level

 

 

 

 

 

Altitude1

Storage Range

30.5 m (100 ft.) below sea level

3000 m (9840 ft.) above sea level

 

 

 

 

 

 

Transit Range

30.5 m (100 ft.) below sea level

 

12,000 m (40,000 ft.) above sea level

 

 

 

 

 

 

1If you plan to operate the drive module or E2400 command module at altitudes between 1000 m (3280 ft.) and 3000 m (9850 ft.), lower the environmental temperature 1.7º C (3.3º F) for every 1000 m (3280 ft.) above sea level.

Drive Module Site Preparation Guide

17

Image 25
Contents Drive Module Trademark Acknowledgments Drive Module Site Preparation Guide Part Number DF1153-E1 Contents Drive Module Site Preparation Guide List of Figures List of Tables Intended Readers About This BookTerminology Used in This Book Content and OrganizationController module or controller tray Term Definition Usage ExamplesGeneral Documentation Documentation SetHardware Documentation Software DocumentationTools and Equipment You May Need Preparatory TasksArea Requirements WeightsESM Unit Maximum1 Unit Empty2 Unit Shipping3 WeightKg 3.8 lb Command Module, deskside Unit Maximum Unit Drive-Ready Shipping Weight1 Unit Maximum Unit Empty Unit Shipping Weight2 Weight3Dimensions E3300 Drive Module Dimensions Drive Module Site Preparation Guide Unit Carton Height Carton Width Carton Depth Airflow Drive Module or E2400 Command Module AirflowElement Unit of Measure E3300 and FC-1 FC-1 14x and E2400 Environmental RequirementsDrive Module and E2400 Command Module Heat Dissipation Site Wiring and Voltages Site Wiring RequirementsNominal Minimum Input Power 50 Hz 60 HZ Nominal MinimumE3300 Drive Module Drive Module Power RequirementsUnit of Measure Requirement InternationalPower Cord Routing USA FC-1 10x Drive Module and E2400 10x Command ModuleDrive Module Power Supplies Command AC Distribution Boxes FC-1 14x Drive Module and E2400 14x Command Module Power Cord Routing E3300 Interface Cables Drive Module Cable RequirementsOrder Information Cable Description Part Length Number006-1086473 Meter Index Index-2 Drive Module Site Preparation Guide Operating current E2400 10x 23 E3300 21 E4400 Index-4 Drive Module Site Preparation Guide Drive Module Site Preparation Guide Index-5 Index-6 Drive Module Site Preparation Guide