Guardian Technologies 004988-4 Control Console Components, ‹ 3.2.1 AUTO/OFF/MANUAL Switch

Page 15

MANUAL — The control board will start and run the generator whenever the switch is in the manual position.

AUTO — The control board will monitor the two- wire start circuit. When a two-wire start is issued the control board will immediately start and run the gen- erator. Whe the two-wire start is removed the control board will immediately stop the generator.

NOTE:

If the generator is installed in conjunction with an engineered GTS type transfer switch, refer to the applicable transfer switch manual for exact oper- ating parameters and timing sequences.

3.2CONTROL CONSOLE

COMPONENTS

The components of a home standby generator control console (Figure 3.1) are as follows:

‹3.2.1 AUTO/OFF/MANUAL SWITCH

Use this three-position switch as follows:

Set the switch to AUTO for fully automatic opera- tion. See “Automatic Operation” (Section 3.6).

Set switch to MANUAL position to crank and start the generator engine.

Set switch to OFF position to shut down an operat- ing engine. With OFF selected, operation will not be possible.

Figure 3.1 - Home Standby Generator Panel

Section 3 - Operation

Liquid-cooled 30 kW Generators

DANGER

With switch set to AUTO, engine can crank and start suddenly without warning. Such automatic start up normally occurs when utility source voltage drops below a pre-set level. To prevent possible injury that might be caused by such sudden starts, set AUTO/OFF/MANUAL switch to OFF before working on or around the unit. Then, place a “DO NOT OPERATE” tag on control console.

‹3.2.2 FAULT INDICATOR LED

This LED goes ON when one or more of the following engine faults occurs and when engine shuts down.

Low Oil Pressure

Overcrank

Low Battery

Overspeed/RPM Sensor Loss

High Coolant Temperature/Low Coolant Level

See Section 1.7 for further explanation of engine pro- tection functions.

‹3.2.3 15 AMP FUSE

Fuse protects the control console’s DC control circuit against electrical overload. If the fuse has melted open because of an overload, engine cranking and startup cannot occur. If the fuse needs to be replaced, use only an identical 15-amp replacement fuse. (Type AGC)

‹3.2.4 4.0 AMP INLINE FUSE

SET EXECISER TIME SWITCH

LED INDICATORS:

FLASHING GREEN LED = NO UTILITY SENSE

5 FLASHING RED LED'S = EXERCISER NOT SET

(IN AUTO MODE ONLY) SOLID GREEN LED = SYSTEM READY, UTILITY POWER ON RED LED'S = INDIVIDUAL FAULT

(SEE OWNER'S MANUAL FOR COMPLETE LED DETAILS)

 

 

OVER CRANK

RED LED

 

 

 

SE

 

SE

 

U

F

F U

 

 

 

AUTO

 

OFF

 

 

 

 

 

OFF

 

ON

 

 

 

SET

MANUAL

GREEN LED

EXERCISE

TO SET EXERCISER TIME

TIME

1) PLACE AUTO/OFF/MANUAL SWITCH TO AUTO POSITION.

0E7194

This fuse protects the battery charger against electri- cal overload. If the fuse needs to be replaced, use only an identical 4 amp replacement fuse (type AG).

NOTE:

This fuse will not remove the + battery input power from the PCB when it opens. This means the exercise timer will not be reset.

‹3.2.5 SET EXERCISE TIME SWITCH

 

AUTO/OFF/MANUAL

4A FUSE

SWITCH

 

BATTERY

15A FUSE

CHARGER

MAIN

 

POWER

This switch allows programming the generator to start and exercise automatically. “See Weekly Exercise Cycle.”

‹3.2.6 SYSTEM READY LED

The System Ready LED (green) has two main pro- poses. First, the LED will be ON when the AUTO/ OFF/MANUAL switch is in the AUTO position, utility is present, and there are no system alarms. This ON state indicates the system is fully ready for automatic operation.

13

Image 15 Contents
Liquid-cooled, Prepackaged Standby Generators Introduction Authorized Service Dealer Location‹ Operation and Maintenance ‹ HOW to Obtain ServiceTable of Contents  Warning   Electrical Hazards  Generator AC Connection Systems Transfer SwitchGenerator Automatic System OperationLOW OIL Presure Switch LOW Coolant Level Switch ‹ 1.7.2 High Coolant Temperature Switch‹ 1.7.1 LOW OIL Pressure Switch ‹ 1.7.3 LOW Coolant Level SwitchLifting the Generator Unpacking‹ 1.10.2 Engine Specifications SpecificationsReconfiguring the Fuel System ‹ 1.10.1 Generator SpecificationsEngine OIL Recommendations Torque SpecificationsStandby Generator Installation Before InstallationGenerator Mounting Support Basic Standby Electric System‹ 2.1.2 Other Published Standards Grounding the Generator Transfer Switch Signal ConnectionsEmergency Circuit Isolation Method Total Circuit Isolation MethodBattery Installation Preparation Before START-UP‹ 2.9.2 GTS-TYPE ATS Using AN Engineered GTS Transfer Switch Control Console Components ‹ 3.2.1 AUTO/OFF/MANUAL Switch‹ 3.2.2 Fault Indicator LED ‹ 3.2.5 SET Exercise Time SwitchAutomatic Operation AdjustmentsManual Transfer START-UP Engine Governor Retransfer and ShutdownCooling System Weekly Exercise CycleChecking Fluid Levels Overload Protection for Engine DC Electrical System‹ 4.5.10 Changing Engine OIL ‹ 4.5.11 Changing the Engine AIR Cleaner‹ 4.5.8 Check FAN Belt ‹ 4.5.9 Inspect Engine Governor‹ 4.5.13 Coolant Change Miscellaneous Maintenance‹ 4.6.3 Battery Maintenance ‹ 4.6.1 Cleaning the Generator‹ Periodic Replacement Parts ‹ 4.6.4 Battery ReplacementService Maintenance Interval Information Scheduled MaintenanceLevel Maintenance Level Problem Cause Correction Troubleshooting PointsLiquid-cooled 30 kW Generators Installation Diagram Size AWG Transfer SwitchAUTO/OFF/MANUAL Switch SET Exerciser SwitchOn PCB Otherwise Noted AS ShownBAT Ignition CoilSWITCH, AUTO/OFF/MANUAL SWITCH, SET ExerciserDPE Starter Motor GOV 12V Battery REDALT DEGEngine Foot Hold Down Battery Boot Battery CableBattery Post Cover Baclk Battery Post Cover RED +To a To B Plcs Duct Discharge LH Front Assy Wire 14AWG 7.5 #0 GRN/YELIntake Duct HSB Duct Discharge RH FrontPage Cover Front Panel HSB Assy 2A 12V UL BatteryControl BOX HSB Decal AVR CoverCooled 30 kW Drawing No Exploded Bracket DC ALT 3.0L Ford Wire SET 3.0L Ford notNot SHOWN-USED to Hold OIL Drain Assembly Coil Ignition 3.0L FordFrame Side Support Radiator HSB Tank Coolant RecoveryRadiator R-IN,L-OUT Venturi 3.0L Ford HSBTo B Washer Flat 5/16 Zinc Weldment Mounting BaseFlange Fuel Inlet Assy Regulator 3.0L NG or LPVLocktight Rotor 39030AD1 HSB Tecum Rotor 390 15KW 1P Direct HSB 2.5L FordRotor 390 20KW 1P Direct HSB 2.5L Ford Rotor 390 25KW 1P Direct HSB 2.5L FordGasket Exhaust Ring Exhaust Flange 2 PipePipe Muffler OUT Washer Lock 3/8 SSAdapter Carburetor W/PVC Conn Plate AIR Cleaner AdapterElement AIR Cleaner Cover AIR CleanerWarranty Schedule