3.7WEEKLY EXERCISE CYCLE

The engine control board will start and run the gen- erator once every seven days for approximately 12 minutes. If utility should fail during this exercise period, the engine control board will transfer the load to the generator output and continue to run until util- ity returns.

On the day, and at the time of day chosen for the generator to exercise, set the weekly exercise cycle as follows:

1.Place the AUTO/OFF/MANUAL switch in the AUTO position.

2.Press and hold the “Set Exercise” switch for three seconds, then release.

At this time all five red LEDs will flash for approxi- mately 10 seconds, then the engine will start and run for it’s 12 minute exercise period, then shut down. The generator will now start and run each week at the same time.

If DC power to the control board is lost, the weekly exercise setting will be lost. This is indicated by all five red LEDs continually flashing. In this state the generator will still start and run in manual mode, or automatically start and run if UTILITY is lost while in Auto mode, but it will not perform a weekly exercise cycle.

If a failure occurs while running in this mode, the five red LEDs will stop flashing, the individual fault LED will turn on and the engine will shut down. Once the AUTO/OFF/MANUAL switch has been switch to OFF, the individual fault LED will turn OFF and the five red LEDs will begin flashing to show exercise has still not been set.

Figure 3.2 - “Set Exercise” Switch

 

 

S

 

 

 

S

 

FUSE

F

U

F

 

F

U

F

 

S

 

 

S

E

 

E

 

 

 

 

FUSE

 

 

U

4A

 

S

E

 

S

E

 

U

 

15A

 

U F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BAT.

MAIN

CHARGER

 

 

AUTO

OFF

 

 

OFF

ON

 

SET

MANUAL

EXERCISE

 

TIME

 

Section 4 — Maintenance

Liquid-cooled 30 kW Generators

4.1MAINTENANCE PERFORMED BY AUTHORIZED SERVICE FACILITIES

‹EVERY THREE MONTHS

1.Check battery state of charge and condition.

2.Inspect and test fuel system.

3.Check transfer switch.

4.Inspect exhaust system.

5.Check engine ignition system.

6.Check fan belts.

‹ONCE EVERY SIX MONTHS

1.Test Engine Safety Devices (low oil pressure, low coolant level, high coolant temperature).

‹ONCE ANNUALLY

1.Test engine governor. Adjust or repair, if needed.

2.Clean, inspect generator.

3.Flush cooling system.

‹FIRST 100 OPERATING HOURS

1.Change engine oil and oil filter. (After initial change, service engine oil and filter at 150 operat- ing hours or 6 months, whichever comes first.)

2.Retorque cylinder head. (See Torque Specs, Section 1.13.)

3.Retorque intake and exhaust manifold. (See Torque Specs, Section 1.13.)

‹EVERY 500 OPERATING HOURS

1.Service air cleaner.

2.Check starter.

3.Check engine DC alternator.

4.2COOLING SYSTEM

Air intake and outlet openings in the generator com- partment must be open and unobstructed for contin- ued proper operation. This includes such obstruc- tions as high grass, weeds, brush, leaves and snow.

Without sufficient cooling and ventilating air flow, the engine/generator quickly overheats, which causes it to shut down. (See Section 6 for installation drawings and vent locations.)

The exhaust system parts from this product get extremely hot and remain hot after shutdown. High grass, weeds, brush, leaves, etc. must remain clear of the exhaust. Such materials may ignite and burn from the heat of the exhaust system.

15

Image 17
Contents Liquid-cooled, Prepackaged Standby Generators ‹ Operation and Maintenance Authorized Service Dealer Location‹ HOW to Obtain Service IntroductionTable of Contents  Warning   Electrical Hazards  Generator Transfer SwitchAutomatic System Operation Generator AC Connection Systems‹ 1.7.1 LOW OIL Pressure Switch ‹ 1.7.2 High Coolant Temperature Switch‹ 1.7.3 LOW Coolant Level Switch LOW OIL Presure Switch LOW Coolant Level SwitchLifting the Generator UnpackingReconfiguring the Fuel System Specifications‹ 1.10.1 Generator Specifications ‹ 1.10.2 Engine SpecificationsStandby Generator Installation Torque SpecificationsBefore Installation Engine OIL Recommendations‹ 2.1.2 Other Published Standards Generator Mounting SupportBasic Standby Electric System Emergency Circuit Isolation Method Transfer Switch Signal ConnectionsTotal Circuit Isolation Method Grounding the Generator‹ 2.9.2 GTS-TYPE ATS Battery InstallationPreparation Before START-UP Using AN Engineered GTS Transfer Switch ‹ 3.2.2 Fault Indicator LED ‹ 3.2.1 AUTO/OFF/MANUAL Switch‹ 3.2.5 SET Exercise Time Switch Control Console ComponentsManual Transfer START-UP Engine Governor AdjustmentsRetransfer and Shutdown Automatic OperationCooling System Weekly Exercise CycleChecking Fluid Levels Overload Protection for Engine DC Electrical System‹ 4.5.8 Check FAN Belt ‹ 4.5.11 Changing the Engine AIR Cleaner‹ 4.5.9 Inspect Engine Governor ‹ 4.5.10 Changing Engine OIL‹ 4.6.3 Battery Maintenance Miscellaneous Maintenance‹ 4.6.1 Cleaning the Generator ‹ 4.5.13 Coolant Change‹ Periodic Replacement Parts ‹ 4.6.4 Battery ReplacementService Maintenance Interval Information Scheduled MaintenanceLevel Maintenance Level Problem Cause Correction Troubleshooting PointsLiquid-cooled 30 kW Generators Installation Diagram AUTO/OFF/MANUAL Switch Transfer SwitchSET Exerciser Switch Size AWGBAT Otherwise Noted AS ShownIgnition Coil On PCBDPE SWITCH, AUTO/OFF/MANUALSWITCH, SET Exerciser ALT 12V Battery REDDEG Starter Motor GOVEngine Foot Battery Post Cover Baclk Boot Battery CableBattery Post Cover RED + Hold Down BatteryTo a To B Plcs Intake Duct HSB Assy Wire 14AWG 7.5 #0 GRN/YELDuct Discharge RH Front Duct Discharge LH FrontPage Control BOX HSB Assy 2A 12V UL BatteryDecal AVR Cover Cover Front Panel HSBCooled 30 kW Drawing No Exploded Not SHOWN-USED to Hold OIL Drain Assembly Wire SET 3.0L Ford notCoil Ignition 3.0L Ford Bracket DC ALT 3.0L FordFrame Radiator R-IN,L-OUT Tank Coolant RecoveryVenturi 3.0L Ford HSB Side Support Radiator HSBTo B Flange Fuel Inlet Weldment Mounting BaseAssy Regulator 3.0L NG or LPV Washer Flat 5/16 ZincLocktight Rotor 390 20KW 1P Direct HSB 2.5L Ford Rotor 390 15KW 1P Direct HSB 2.5L FordRotor 390 25KW 1P Direct HSB 2.5L Ford Rotor 39030AD1 HSB TecumPipe Muffler OUT Exhaust Flange 2 PipeWasher Lock 3/8 SS Gasket Exhaust RingElement AIR Cleaner Plate AIR Cleaner AdapterCover AIR Cleaner Adapter Carburetor W/PVC ConnWarranty Schedule

004988-4 specifications

Guardian Technologies 004988-4 is a cutting-edge air purifier designed to create a cleaner and healthier indoor environment. With increasing concerns about air quality in our homes and workplaces, this innovative device provides an effective solution to combat airborne pollutants and allergens.

One of the standout features of the Guardian Technologies 004988-4 is its powerful 4-in-1 filtration system. This system includes a pre-filter that captures larger particles like dust and pet hair, a true HEPA filter that traps 99.97% of particles as small as 0.3 microns, an activated carbon filter that helps reduce odors, and a UV-C light that targets bacteria and viruses. This comprehensive filtration method ensures that the air you breathe is free from harmful contaminants.

Another important characteristic of the Guardian Technologies 004988-4 is its large coverage area. This air purifier is capable of effectively purifying air in rooms up to 300 square feet, making it suitable for bedrooms, living rooms, and office spaces. Its compact and modern design allows it to blend seamlessly with various interior styles, while its lightweight construction makes it easy to move from one room to another.

Additionally, the Guardian Technologies 004988-4 features a quiet operation mode, ensuring that it can run continuously without disrupting daily activities. It also comes equipped with multiple fan speeds, allowing users to customize the airflow based on their preferences and air quality needs. The unit is designed for user-friendly operation, with simple controls that make it easy to switch between modes and adjust settings.

Energy efficiency is another highlight of the Guardian Technologies 004988-4. It is constructed to consume low energy while maintaining high performance, making it an eco-friendly choice for air purification.

In summary, the Guardian Technologies 004988-4 offers a robust combination of features, including a 4-in-1 filtration system, wide coverage area, quiet operation, and energy efficiency. These characteristics make it a reliable and effective air purifying solution that contributes to a healthier indoor environment, promoting overall well-being for users and their families.