Guardian Technologies 004582-2 owner manual 1 120 VAC, 20 AMP, Duplex Receptacle

Page 9

Section 2 – Operation

Commercial-Industrial-Residential Portable Generator System

2.2 CORD SETS AND CONNECTION PLUGS

2.2.1 120 VAC, 20 AMP, DUPLEX RECEPTACLE

This is a 120 Volt outlet protected against overload by a 20 Amp push-to-reset circuit breaker (Figure 7). Use each socket to power 120 Volt AC, single phase, 60 Hz electrical loads requiring up to a combined 2400 watts (2.4 kW) or 20 Amps of current. Use only high quality, well-insulated, 3-wire grounded cord sets rated for 125 Volts at 20 Amps (or greater).

Keep extension cords as short as possible, preferably less than 15 feet long, to prevent voltage drop and possible overheating of wires.

Figure 7 - 120 Volt AC, 20 Amp, Duplex Receptacle

2.2.2 120 VAC, 20 AMP, GFCI RECEPTACLE

This unit is equipped with a ground fault circuit interrupter (GFCI). This device meets applicable federal, state and local codes (Figure 8).

A GFCI receptacle is different from conventional receptacles. In the event of a ground fault, a GFCI will trip and quickly stop the flow of electricity to prevent serious injury.

Definition: Instead of following its normal safe path, electricity passes through a persons body to reach the ground. For example, a defective appliance can cause a ground fault.

A GFCI receptacle does NOT protect against circuit overloads, short circuits, or shocks. For example, electric shock can still occur if a person touches charged electrical wires while standing on a non- conducting surface, such as a wood floor.

Figure 8 - 120 VAC, 20 Amp GFCI Receptacle

Testing the GFCI: Test the GFCI outlet every month as follows:

Plug a test lamp into the receptacle.

Start the generator, the test lamp should be on.

Press the “Test” button located on the front of the receptacle to trip the device.

This should stop the flow of electricity making the lamp shut off. The yellow trip indicator should now be on.

To restore the flow of electricity, press the “Reset” button on the front of the receptacle. If the GFCI does not perform in this manner, do not use the receptacle. Contact a local service dealer.

This outlet is protected against overload by a 20A push-to-reset circuit breaker. Use the outlet to power 120V AC, single-phase, 60 Hz, electrical loads requiring up to a combined 2400 watts (2.4 kW) or 20 amps of current.

2.2.3 120 VAC, 30 AMP RECEPTACLE

Use a NEMA L5-30 plug with this receptacle. Connect a 3-wire cord set rated for 125 Volts AC at 30 Amps (or greater) to the plug (Figure 9).

Figure 9 - 120 VAC, 30 Amp Receptacle

7

Image 9
Contents Ultra Source 11.1 Section Exploded Views and Parts Lists11.2 11.3Introduction Read this Manual ThoroughlyNever add fuel while unit is running  General Hazards  Important Safety Instructions Explosion Hazards   Electrical Hazards  Fire Hazards  Standards IndexAccessory BOX AssemblyUnpacking Assembling the Wheel KITHandle Assembly Battery ConnectionFuel Tank Tank holds 16 U.S. gallons of fuel Know the Generator2 120 VAC, 20 AMP, Gfci Receptacle 1 120 VAC, 20 AMP, Duplex Receptacle5 12 Volt DC, 10 AMP Receptacle HOW to USE the GeneratorGrounding the Generator 50 aConnecting Electrical Loads DON’T Overload the GeneratorWattage Reference Guide Adding Gasoline Adding Engine OILSynthetic oil should only be used after first oil change Stopping the Engine To Start the EngineAutomatic Idle Control Charging a BatteryInitial START-UP Sensing LOW OIL PressureProduct Specifications Maintenance ScheduleGenerator Specifications Engine SpecificationsGeneral Recommendations Service AIR Cleaner Clean Spark Arrestor ScreenReplacing the Spark Plug Install new valve cover gasket Re-attach the valve cover To adjust valve clearanceGeneral To check valve clearanceStore the unit in a clean, dry place  Avoid spray from spark plug holes when cranking engineLong Term Storage Other Storage TipsTroubleshooting Guide Electrical Data Wiring Diagram Drawing No G0731 Electrical Data Handle, Frame & Wheel Kit Drawing No E0695-B QTY Description Control Panel Drawing No G0727-B SWITCH, Rocker -/0 Generator Drawing No G0742-A Exploded Views and Parts Lists Generator Drawing No G0742-A GT-760/990 Engine Drawing No E8589-W Part Sleeve Exploded Views and Parts Lists WINGNUT, Airbox MANUFACTURER’S Emission Control System Warranty Coverage Emission Control System Warranty Warranty Schedule