16
Operating SpaYour
The “FILTER 1” indicator icon will light when filter 1 is running.
•The second filter cycle is automatically activated at 8:00 PM and operates the pump until 10:00 PM.
The “FILTER 2” indicator icon will light when filter
2 is running.
The pump and the ozone generator will run during filtration. At the start of each filter cycle, the blower will run on highest speed for 30 seconds to clean out the air channels. The lowest speed of pump 2 and pump 3 will run for five minutes. In the event of power loss or shut down, the time of day will need to be reset for filter cycles to run according to your desired programming.
Clean up Cycle
When the pump or blower is turned on by a button press, a
Ozone
This is an optional feature. On most systems, the ozone
generator (if installed) runs during filter cycles (except
when pump 1 is operating at high speed on a
the pump runs. If your system is configured with the
optional ozone disable feature, the ozone generator will turn off for one hour any time a function button
(“JETS 1”, “JETS 2”, “OPTION” etc.) is pressed.
Freeze Protection
If the temperature sensors detect a drop to 44°F
within the heater, the pump automatically activates to provide freeze protection. The equipment stays on until four minutes after the sensors detect that
the spa temperature has risen to 45°F or higher. In
colder climates, an optional additional freeze sensor may be added to protect against freeze conditions that may not be sensed by the standard sensors. Auxiliary freeze sensor protection acts similarly except with the temperature thresholds determined by the switch and without a
2010 Portable Spa
www.calspas.com | LTR20101000, Rev. C |