3Com 8807, 8814, 8810 Installation Lightning Arrester for Network Port, Is not well grounded yet

Models: 8810 8814 8807

1 97
Download 97 pages 32.87 Kb
Page 96
Image 96

96CHAPTER A: LIGHTNING PROTECTION OF THE SWITCH

the lightning arrester of power is running and the function of lightning protection has taken effect.

Pay adequate attention if the red LED is on. You should correctly locate the

 

problem, whether it is caused because the ground wire of the arrester is not

 

well grounded or because the live and zero wires are connected in reverse

 

direction. You may check that in the following way. When the red LED is on,

 

use a multimeter to examine polarity at the power socket of the arrester. If it is

 

same to that of the power socket in the equipment room, it means that

 

arrester is not well grounded. If it is adverse to that of the power socket in the

 

equipment room, it means that the power socket of the arrester is set to the

 

reverse polarity. In this case, you should open the power socket of arrester to

 

correct polarity. After that, if the red LED still alarms, it means that the arrester

 

is not well grounded yet.

Installation of

 

Lightning Arrester for

 

Network Port

 

n

Lightning arrester for network port is specially designed for the Ethernet port of

10/100M electrical interface (RJ-45 connector is adopted in this case).

c CAUTION: Lightning arrester for network port will not be provided along with the switch, and you should purchase it by yourself if needed.

If an outdoor network cable should be led to the switch, please serially connect the lightning arrester for network port before you plug this cable into the interface on the switch, in case of the possibility that the switch may be damaged due to lightning strike.

Required tools

Phillips screwdriver or Flat-module screwdriver

Multimeter

Tilted wire cutter

Installation procedure

Step 1: Tear the protection paper at one side of the double faced adhesive tape apart from the tape, and stick the tape on the surface of the arrester. Tear the protection paper at another side apart from the tape, and stick the arrester onto the chassis of the switch. The arrester should be attached on the chassis as close to the grounding screw as possible.

Step 2: According to the distance to the grounding screw of the switch, cut the ground wire of the arrester, and securely tightening its ground wire to the grounding screw of the switch.

Step 3: Use the multimeter to measure whether the ground wire of the arrester contacts well with the grounding screw of chassis.

Step 4: According to the instruction of arrester for network port, connect the arrester with switch by the cables (be carefully with the cable direction. Outdoor network cable should be inserted into the arrester‘s IN end, and the cable

Page 96
Image 96
3Com 8807, 8814, 8810 Installation Lightning Arrester for Network Port, Is not well grounded yet, Installation procedure