TABLE 6. TECHNICAL DATA VENTING

TABLE 6. TECHNICAL DATA VENTING

TYPE B GAS VENT

Multiple Gas Fired Tank-Type Heaters

When venting multiple tank type heaters using Type B vent pipe, follow the installation diagram (figure 4) and tables below which give sizing and data based upon NFPA 54/ANSI Z223. 1992.

MODEL BTN-120

Input: 120,000 Btu/hr

 

 

 

 

Total Vent Height (Feet)

 

 

 

 

Vent Connector Size: 5 inches

 

 

6

8

10

15

20

 

30

50

100

 

 

Input Btu/hr

 

Rise

 

Vent Connector Diameter (Inches)

 

 

 

120,000

 

1 Ft.

6

6

 

5

5

5

 

5

5

5

 

 

120,000

 

2 Ft.

5

5

 

5

5

5

 

5

5

5

 

 

120,000

 

3 Ft.

5

5

 

5

5

5

 

5

5

5

 

Number of

Combined Input

 

 

 

 

 

 

 

 

 

 

 

 

 

BTN 120 Heaters

in Thousands of Btu/hr

 

 

Manifold and Common Vent Diameter (Inches)

2

240,000

 

 

7

7

6

6

6

 

6

6

6

 

3

360,000

 

 

8

8

7

7

7

 

6

6

6

 

4

480,000

 

 

9

9

9

8

8

 

7

7

6

 

MODEL BTN-154

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input: 154,000 Btu/hr

 

 

 

 

Total Vent Height (Feet)

 

 

 

 

Vent Connector Size: 6 inches

 

 

6

8

10

15

20

 

30

50

100

 

 

Input Btu/hr

 

Rise

 

Vent Connector Diameter (Inches)

 

 

 

154,000

 

1 Ft.

6

6

6

6

6

 

6

6

6

 

 

154,000

 

2 Ft.

6

6

6

6

6

 

6

6

6

 

 

154,000

 

3 Ft.

6

6

6

6

6

 

6

6

6

 

Number of

Combined Input

 

 

 

 

 

 

 

 

 

 

 

 

 

BTN 154 Heaters

in Thousands of Btu/hr

 

 

Manifold and Common Vent Diameter (Inches)

2

308,000

 

 

7

7

6

6

6

 

6

6

6

 

3

462,000

 

 

8

8

7

7

7

 

6

6

6

 

4

616,000

 

 

9

9

9

8

8

 

7

7

6

 

MODEL BTN-180,199, 200

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input: 180,000, 190,000 and 199,000 Btu/hr

 

 

 

Total Vent Height (Feet)

 

 

 

 

Vent Connector Size: 6 inches

 

 

6

8

10

15

20

 

30

50

100

 

 

Input Btuh/hr

 

Rise

 

Vent Connector Diameter (Inches)

 

 

 

180,000

 

1 Ft.

7

7

6

6

6

 

6

6

6

 

 

190,000

 

1 Ft.

7

7

7

6

6

 

6

6

6

 

 

199,000

 

1 Ft.

7

7

7

6

6

 

6

6

6

 

 

180,000

 

2 Ft.

6

6

6

6

6

 

6

6

6

 

 

190,000

 

2 Ft.

7

6

6

6

6

 

6

6

6

 

 

199,000

 

2 Ft.

7

7

6

6

6

 

6

6

6

 

 

180,000

 

3 Ft.

6

6

6

6

6

 

6

6

6

 

 

190,000

 

3 Ft.

6

6

6

6

6

 

6

6

6

 

 

199,000

 

3 Ft.

6

6

6

6

6

 

6

6

6

 

Number of

Combined Input

 

 

 

 

 

 

 

 

 

 

 

 

 

BTN Heaters

in Thousands of Btu/hr

 

 

Manifold & Common Vent Diameter (Inches)

2

360,000

 

 

7

7

6

6

6

 

6

6

6

 

380,000

 

 

7

7

7

6

6

 

6

6

6

 

 

398,000

 

 

6

7

7

6

6

 

6

6

6

 

 

540,000

 

 

7

6

6

6

6

 

6

6

6

 

3

570,000

 

 

7

6

6

6

6

 

6

6

6

 

 

597,000

 

 

6

7

6

6

6

 

6

6

6

 

 

720,000

 

 

6

6

6

6

6

 

6

6

6

 

4

760,000

 

 

6

6

6

6

6

 

6

6

6

 

 

796,000

 

 

6

6

6

6

6

 

6

6

6

 

9