A.O. Smith BTN 120 THRU 400/A Series One Or Two Temperature - One Heaters,High Temperature

Models: BTN 120 THRU 400/A Series

1 32
Download 32 pages 24.85 Kb
Page 16
Image 16
ONE OR TWO TEMPERATURE - ONE HEATERS,HIGH TEMPERATURE

ONE OR TWO TEMPERATURE - ONE HEATERS,HIGH TEMPERATURE

STORAGE WITH OR WITHOUT RECIRCULATION

HEATER WITH OR WITHOUT MIXING VALVE

DANGER

TEMPERATURE SETTING SHOULD NOT

EXCEED SAFE USE TEMPERATURE AT

FIXTURES. SEE WATER TEMPERATURE

CONTROL WARNING ON PAGE 25. IF HIGHER

PREHEAT TEMPERATURES ARE NECESSARY

TO OBTAIN ADEQUATE BOOSTER OUTPUT,

ADD AN ANTI-SCALD VALVE FOR HOT WATER

SUPPLIED TO FIXTURES.

HEATER WITH MIXING VALVE AND RECIRCULATED SANITIZING LOOP

* PIPE RELIEF VALVE TO OPEN DRAIN.

NOTE 1:

TOGGLE SWITCH CONTROLS 180°F (82°C) NOTE 2: INSTALL LINE TEMPERATURE CONTROL

WATER CIRCULATION. INSTALL ON OR CLOSE

IN AN UNINSULATED TEE BEYOND THE

TO DISHWASHING MACHINE. TOGGLE SWITCH

DISHWASHING MACHINE TAKEOFF IN

INSTALL IN ACCORDANCE WITH LOCAL CODES.

CIRCULATING RETURN LINE CONNECTIONS.

-TEMPERED WATER LOOP, IF USED, CONNECT TO POINT “R”.

-STORED TEMPERATURE WATER LOOP, IF USED, CONNECT TO COLD WATER INLET.

MUST BE CLOSED (ON) DURING THE RINSE

THE SANITIZING LOOP. CONTROL

OPERATION AND OPEN (OFF) WHEN

SHOULD BE SET AT 185°F (85°C).

DISHWASHER IS NOT OPERATING OR WHEN

 

ON LONG STANDBY.

NOTE 3: ADJUST PLUG COCK SO THE SANITIZING

 

LOOP FLOW RATE DOES NOT CAUSE

 

UNNECESSARY TURBULENCE IN THE TANK.

CAUTION: IF BUILDING COLD WATER SUPPLY HAS A BACKFLOW PREVENTER, CHECK VALVE OR WATER METER WITH CHECK VALVE. PROVISIONS FOR THERMAL EXPANSION OF WATER IN THE HOT WATER SYSTEM MUST BE PROVIDED.