Instruction manual SGS 31
is
Explanation of type of appliance
Note
Make sure that the chimney discharges into an area where this is permitted
for this category of appliance.
3.10.3 Concentric connections
The table shows the requirements for concentric systems.
Warning
Install flue gas discharge pipe runs with a run-off of 5 mm per metre.
Flue gas discharge requirements for concentric systems (C13, C33)
Caution
Both conditions stated in the table must be fulfilled.
Even if there are less bends than the stated maximum, the maximum pipe
length may not be exceeded.
Even if the total pipe length is less than the stated maximum, the maximum
number of bends may not be exceeded.
The following example illustrates how to use the table.
Type of appliance Description
B23 Air for combustion is drawn from the boiler room.
C13 Concentric and / or parallel wall flue terminal
C33 Concentric and / or parallel roof flue terminal
C43 Appliances on common air supply and flue gas discharge (concentric and / or
parallel) in multi-storey building.
C53 Air supply and flue terminal types mixed.
C63 Appliances supplied without flue components and / or terminal. These
appliances must be installed in compliance with local regulations.
Appliance Diameter Maximum length Maximum
number of 90°
bends
SGS 80 130/200mm 15m 3
SGS 100 130/200mm 15m 3