Instruction manual SGS 33
is
Concentric wall flue terminal specifications C13
Concentric roof flue terminal specifications C33
3.10.4 Parallel connections
The table states the maximum pipe lengths for parallel systems. The maximum
pipe length depends on the chosen diameter.
Warning
Install flue component pipe runs with a run-off of 5mm per metre.
Table of pipe lengths
Subject Description
Wall flue terminal set:
1x wall flue terminal (incl. wall flange &
clamping ring)
1x pipe 500mm
1x bend 90°
Item No. 0302 326 1
Construction Concentric
Manufacturer Muelink & Grol
Type M2000 MDV SEC
Pipe material Construction Concentric
Flue gas
discharge
Thick-walled aluminium with lip ring seal
Air supply Thin-walled galvanised sheet steel
Pipe diameters Flue gas
discharge
Ø 130mm
Air supply Ø 200mm
1 No other wall flue terminal is permitted. Use this item number to order the wall conduit set from supplier,
manufacturer or wholesaler.
Subject Description
Roof flue terminal set:
1x wall flue terminal (incl. clamping
ring)
1x pipe 1000mm
1x mounting flange
Item No. 0306 855 1
Construction Concentric
Manufacturer Muelink & Grol
Type M2000 DDV SEC
Pipe material Construction Concentric
Flue gas
discharge
Thick-walled aluminium with lip ring seal
Air supply Thin-walled galvanised sheet steel
Pipe diameters Flue gas
discharge
Ø 130mm
Air supply Ø 200mm
1 No other wall flue terminal is permitted. Use this item number to order the wall conduit set from supplier,
manufacturer or wholesaler.
Appliance Diameter1Maximum
total length
Lequivalent
90° bend
Lequivalent
45° bend
SGS 80 130mm 115m 2.4m 1.4m
SGS 100 130mm 60m 2.4m 1.4m