9.3Troubleshooting table for errors visible on the control

46

Instruction manual TWI 35-130 G/TWI 45-190 G

9.3Troubleshooting table for errors visible on the control

Errors visible on the control

Light pulses

Cause

Solution

Remark

 

 

 

 

1 (SC)

Defective air pressure

Replace the air pressure switch.

The error will automatically disappear when the air pressure

Air pressure switch

switch

 

 

switch opens again.

closed

 

 

 

 

 

 

 

 

 

2 (SC)

Break in the cable /

1.

Check the cabling between the air pressure switch and the

Contact the installation engineer if the error cannot be remedied

Air pressure switch is

Open circuit

 

control.

or if it reoccurs. Also contact the installation engineer for replacing

not functioning well

 

2.

Replace the cabling if necessary.

the required parts.

 

 

 

 

 

 

Air pressure switch

1.

Check if the fan is running

 

 

does not close

2.

Check if the hoses are correctly mounted on the air pressure

 

 

 

 

switch.

 

 

 

3.

Check the hoses on the air pressure switch for cracks.

 

 

 

 

Replace the hoses if necessary.

 

 

 

4.

Check if the flue gas discharge is sufficient (3.8 “Air supply

 

 

 

 

and flue gas discharge”).

 

 

 

5.

Check for blockage of the air supply and the flue gas

 

 

 

 

discharge. Remove any blockage.

 

 

 

6.

Check for blockage of the condensation drainage. Remove

 

 

 

 

any blockage.

 

 

 

7.

Measure the pressure difference over the pressure switch.

 

 

 

 

See the table in (10.2 “Prepare maintenance”). Clean the

 

 

 

 

heat exchanger and burner in case of insufficient pressure

 

 

 

 

difference. If the pressure difference is sufficient, check if the

 

 

 

 

air pressure switch closes using a multimeter.

 

 

 

8.

Check the supply voltage. This should be 230VAC

 

 

 

 

(-15% +10%).

 

 

 

 

 

 

Instruction manual - TWI 35-130 G/TWI 45-190 G