Opal Pro to Mod TCP

Output

AB Ethernet

Name

Description

Words

IP

 

 

(Polled)

 

 

 

Word 1

Input Word 0

Status

Bit 0 – Ready to Run (drive is enable

 

 

 

and has 3 phase power)

 

 

 

Bit 1 –Running (start is regulating)

 

 

 

Bit 2 – Full On (starter is phased fully

 

 

 

on)

 

 

 

Bit 3 – Up to Speed (started is

 

 

 

phased fully on and the current is

 

 

 

below 105% of nameplate current as

 

 

 

set in 13.01)

 

 

 

Bit 4 – Reverse

 

 

 

Bit 5 – Jogging

 

 

 

Bit 6 – DC Injecting

 

 

 

Bit 7 – Faulted

 

 

 

Bit 8 – IOC Fault

 

 

 

Bit 9 – MOL Fault

 

 

 

Bit 10 – Phase Loss Fault

 

 

 

Bit 11 – Shear Pin Fault

 

 

 

Bit 12 – Shorted SCR Fault

 

 

 

Bit 13 – Heat Sink OT Fault

 

 

 

Bit 14 – Reserved

 

 

 

Bit 15 – Watch Dog Bit

Word 2

Input Word 1

Current

833 = 500% of motor name plate

 

 

Feedback

current as set in 13.01

Word 3

Input Word 2

Phase Angle

Amount of time phased on in

 

 

Actual

microseconds

Parameter

AB Ethernet

Name

Description

 

IP

 

 

 

1.01

Input Word 3

Current

Current feedback in Amps

1.02

Input Word 4

L1 to L2

Line 1 to Line 2 Voltage in Volts

 

 

Voltage

 

 

1.03

Input Word 5

L1 to L3

Line 1 to Line 3 Voltage in Volts

 

 

Voltage

 

 

1.04

Input Word 6

L2 to L3

Line 2 to Line 3 Voltage in Volts

 

 

Voltage

 

 

1.05

Input Word 7

DI Status

Digital input status

 

 

 

Bit 0 – Start

 

 

 

Bit 1

– Stop

 

 

 

Bit 2

– Jog

 

 

 

Bit 3

– Reverse

 

 

 

Bit 4

– Reset

1.06

Input Word 8

Analog Input

Analog input value in Volts X 100

Page 11

Page 11
Image 11
AB Soft MS6 SERIES user manual Output AB Ethernet Name Description Words Polled, Parameter AB Ethernet Name Description