The event codes are defined in the table below.
# Description Notes
0 no record -
1 aux power unconfig
auxiliary power module present but unconfigured.
2 aux power corrected
auxiliary power module replaced after being missing.
3 aux power missing
auxiliary power module not present but configured.
4 ac1 power restored
ac for main board input restored.
5 ac1 power trouble ac for main board input missing/brownout.
6 ac2 power restored
ac for power module input restored.
7 ac2 power trouble ac for power module input missing/brownout.
8 batttery1 restored battery for main board input restored.
9 batttery1 trouble battery for main board input missing.
10 battery2 restored battery for power module input restored.
11 battery2 trouble battery for power module input m issing.
12 aud1 trb restored audible #1 r estored.
13 aud1 open trouble audible #1 open circuit.
14 aud1 short trouble audible #1 short circuit.
15 aud2 trb restored audible #2 r estored.
16 aud2 open trouble audible #2 open circuit.
17 aud2 short trouble audible #2 short circuit.
18 gnd fault restored ground fault trouble restored to normal.
19 gnd fault present ground fault present.
20 device present addr device trouble: device returns canceling missing trouble
21 device missing addr device trouble: device was polled but not found
22 commun restored
addr device trouble: communication to device has returned to normal
23 bad communication
addr device trouble: communication to device has errors (parity checksum
etc.)
24 restored multiple addr device trouble: multiple devices trouble has cleared
25 multiple devices addr device trouble: multiple devices detected at this address
26 restored device kind
addr device trouble: correct kind of device has b een restored to this
address
27 wrong device kind addr device tr ouble: wrong kind of devices has been found
28 contaminated device
addr device trouble: analog device is contaminated
29 loop module restored
loop mod missing trouble has cleared
30 loop module missing
loop module not in place but there are configured devices on the loops.
31
accessed trouble stored when the configuration menu has been entered
32 factory initialized history stored when a factory initialization has been invoked
33 uart failure history stored when the uart has been corrupted by esd and then re-
initialized.
34 uart restored history stored when preceding trouble has cleared.
35 system reset complete reset including power-down of loops for ten seconds.
36 trouble restored trouble function input restore.
37 trouble input active trouble function input present.
38 process restored process control function input restored.
39 process input active process control function input present.
40 supervisory restored supervisory function input restore.
41 supervisory active supervisory function input present.
42 remote reset release
remote reset function input released.
43 trouble unsilence all troubles unsilenced for all zones.