FS-8700-48 Fike Cheetah Manual Page 28 of 36
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserv er.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll Free: 888-509-1970 email: support@fieldser ver.com
# Description Notes
85 network drill presnt drill state activated from network - all zone only.
86 abort restored abort state for this zone de-activated.
87 abort present abort state for this zone activated.
88 pre-alarm1 restored pre-alarm 1 state for this zone de-activated.
89 pre-alarm1 present pre-alarm 1 state for this zone activated.
90 pre-alarm2 restored pre-alarm 2 state for this zone de-activated.
91 pre-alarm2 present pre-alarm 2 state for this zone activated.
92 network drill restor drill state res tored from network - all zone only.
93 alarm present alarm state for this zone activated.
94 periph #aa missing peripheral device of id#aa is missing.
95 pre-discharge pre-discharge state for this zone activated.
96 periph #aa return periphera l device of id#aa has returned on line.
97 release release state for this zone activated.
98 zone enabled zone disable state for this zone de- activated.
99 zone disabled zone disable state for this zone activated.
100
watermist inactive not used since release state never clears
101
watermist active waterm ist state for this zone activated
102
network alarm unsil network command - unsilence alarms
103
network superv unsil
network command - unsilence supervisories
104
checksum ok ----- zone configuration check sum error restored. zone number appended
to
this message.
105
checksum error -----
zone configuration checksum err or. zone number appended to this
message.
106
network troubl unsil network command - unsilence troubles
107
vesda not configured
trouble event stored when the hli is present but no vesda is configured.
108
vesda configur clear trouble clear event for the above trouble.
109
config menu exited trouble clear event when the configuration menu has been exited
110
aux1 power restored
auxiliary power input trouble restored - main board
111
aux1 power trouble auxiliary power input trouble - m ain board
112
aux2 power restored
auxiliary power input trouble restored - power module
113
aux2 power trouble auxiliary power input trouble - po wer module
114
aud switch disabled enable/disa ble switch for audibles is in the disable position
115
aud switch restored enable/disable switch for audibles has returned to the enable position
116
diagnostics entered indicates the operator has accessed the diagnostic menu selections
117
zone disable restore frcm assigned to zone disable function has cleared
118
zone disable active frcm assigned to zone disable function has activated
119
internal fault device trouble from the 0x08 polling command
120
int fault restored trouble restored from the 0x08 polling command
121
wiring fault-open open circuit fault on supervised circuit: frcm/som/srm
122
wiring fault-short short circuit fault on frcm/som/srm
123
acknowledge switch
acknowledge switch pressed.
124
test point bad analog device fire test point is out of hochiki specified range.
125
calibration restored calibration fault has been restored. device now has valid calibration data.
126
calibration fault fault detected during calibration of this device.
127
configure restored fault restored from som/r2m/srm configuration trouble.
128
configure fault fault detected when configuring som/r2m/srm.
129
reconfigured device addressab le device has been configured
130
enabled device addressable device has been enabled.
131
disabled device addressab le device has been disabled.