Revers ing, 3ø Motor (Elec tric)ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)
IMPORTANT:
NOTES: A.
B.
C.
208 VAC AND 240 VAC ARE NOT THE SAME. When ordering, specify exact voltage.
When fuses are used they must be dual element, time delay, current limiting, class RK1 or RK5 ONLY.
Calculate/determine correct fuse value, by applying either local and/or National Electrical Codes to listed
appliance amp draw data.
Circuit breakers are thermal-magnetic (industrial) type ONLY. For others, calculate/verify correct breaker
size according to appliance amp draw rating and type of breaker used.
Circuit breakers for 3-phase (3Ø) dryers must be 3-pole type.
SERVICE
VOLTAGE PHASE WIRE
SERVICE
APPROX.
AMP DRAW MINIMUM
WIRE SIZE
FUSING CIRCUIT
BREAKER
Dual Element
Time D ela y
60 Hz 50 Hz
60 kW
208 3ø 3 181 — * 250 250
230 3ø 3 — 167 * 200 200
240 3ø 3 159 — * 200 200
380 3ø 4** — 100 * 125 125
400 3ø 4** — 95 * 125 125
416 3ø 4** — 92 * 125 125
460 3ø 3 83 — * 125 125
480 3ø 3 80 — * 100 100
575 3ø 3 66 — * 100 100
72 kW
208 3ø 3 214 — * 300 300
230 3ø 3 — 197 * 250 250
240 3ø 3 188 — * 250 250
380 3ø 4** — 118 * 150 150
400 3ø 4** — 112 * 150 150
416 3ø 4** — 109 * 150 150
460 3ø 3 98 — * 125 125
480 3ø 3 94 — * 125 125
575 3ø 3 78 — * 100 100
* AWG Stranded Wire Type; size wire as per National Electrical Code or local codes. (Motor lead wire is recommended.) 12/10/08
** 3-Wire is available.