1.22 Specifications
Tabl e 2 lists specifications for the circuit breaker panel.
Table 2. Circuit Breaker Panel Specifications
PARAMETER SPECIFICATION REMARKS
Physical
Weight 12 pounds (5.45 kilograms)
Dimensions (HxWxD) 1.75 x 17.13 x 11.0 inches
(44 x 435 x 280 mm)
See Figure6.
Color Putty white
Rack mounting 19- or 23-inch (EIA or
WECO hole spacing)
Flush or with a recess of 1, 2,
3, or 4 inches (25.4, 50.8,
76.2, or 101.6 mm)
Electrical
Operating voltages –24 Vdc nominal Input range: –21 to –30 Vdc
–48 Vdc nominal Input range: –42 to –56 Vdc
Input current 45 Amps max. per bus 90 Amps max. per panel
Circuit breaker rating 5 or 10 Amps Positions are labeled
Circuit breaker positions 7 per bus 14 per panel
Max. circuit breaker size 10 Amps rating 45 Amps per bus
Input terminal type 2-hole compression lug Stud type accepting up to #6
AWG wire
Output terminal type 7-position screw-down barrier
terminal strip
Accepting a variety of wire
up to 12 AWG wire
Alarm contact current 1 Amp max.
Grounding connection Two #10 studs and nuts on
0.625 centers
Environmental
Operating temperature –5º C to +55º C
Storage temperature –45º C to +85º C
Humidity range 0% to 95% humidity No condensation
Altitude range –197 feet (0.06 km) to 13,000
feet (3.96 km) above sea level
Acoustic noise 0 dBA above ambient
Heat dissipation (no load) 1 Watt per bus
Heat dissipation (fully loaded) 30 Watts max. at 25º C ambient