InstallationLTPH-UM-1237-04

Table 2. Terminal Block (TB1)

Terminal

Description

 

 

1

-48V_A

 

 

2

-48V_B

 

 

3

BATTERY RETURN

 

 

4

FGND

 

 

1Remove the fuse(s) in the equipment bay fuse panel for the circuit(s) where the HRM-238 shelf battery wire(s) will terminate.

2Connect one end of the frame ground wire to Terminal 4 (FGND) on TB1 of the HRM-238 shelf and attach the other end of the frame ground wire to the CO ground wire termination point.

3Connect the -48 Vdc CO battery to the HRM-238 shelf (Figure 7):

a Connect a wire to the HRM-238 shelf TB1 Terminal 1 (-48V_A) for Primary CO battery. b Connect a wire to the HRM-238 shelf TB1 Terminal 2 (-48V_B) for Redundant CO battery.

cConnect the battery common wire to HRM-238 shelf TB1 Terminal 3 (BATTERY RETURN) of the HRM-238 shelf and attach the other end to CO battery ground source(s).

dConnect the wire(s) from the HRM-238 TB1 Terminal 1 and Terminal 2 to the CO -48 Vdc power termination point(s).

Terminal 2

Terminal 4 to

to -48 Vdc

frame ground (FGND)

 

 

H0547-B

 

 

 

Terminal 1

Terminal 3 to battery

to -48 Vdc

common (Battery Return)

Figure 7. Connect -48 Vdc and Frame Grounds to TB1

INSTALLING COMMUNICATION WIRING

All wiring and connections for the HRM-238 shelf are on the back. Figure 5 on page 4 shows the shelf backplane and connectors. Connect the NMA wiring from the HRM-238 shelf to each HiGain or Megabit Modem line unit that will be managed using the steps beginning on page 7. Then, use the other connectors in “Connect to a LAN or Interconnect Shelves” on page 9 and “Connect to a Computer, Terminal, or Modem” on page 9 that are appropriate for your application.

6

July 21, 2004

HRM-238 List 1

Page 14
Image 14
ADC HRM-238 L1 user manual Installing Communication Wiring, Terminal Block TB1