Interfaces | RS232 | |||||||
|
| |||||||
|
| Additionally: Communication slot | ||||||
|
| for expansions (e.g. AS/400 / | ||||||
|
| USB / remote signal indicator / | ||||||
|
| SNMP, …) | ||||||
Shutdown software on CD | “CompuWatch” for all common | |||||||
|
| operating systems, e.g. | ||||||
|
| Windows, Linux, Mac, Unix, | ||||||
|
| FreeBSD, Novell, Sun | ||||||
General data |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
Classification | VFI SS 111 acc. to IEC | |||||||
|
| Sustained transformer | ||||||
|
| technology | ||||||
Full load efficiency | > 90% / > 88% |
|
|
| ||||
|
|
|
|
|
|
| ||
Inherent noise (1m distance) |
|
|
|
|
|
|
| |
PROTECT 1.100 | < 55 dB(A) | |||||||
PROTECT 1.150 | < 60 dB(A) | |||||||
PROTECT 1.200 | < 60 dB(A) | |||||||
Cooling type | Forced air cooling through | |||||||
|
| |||||||
Operating temperature range | 0°C to +40°C | |||||||
|
| Recommended: +15°C to +25°C | ||||||
|
| (due to battery system) | ||||||
Storage temperature range | 0°C to +40°C | |||||||
Relative humidity | < 95% (without condensation) | |||||||
Site altitude | Up to 1000 m at nominal output | |||||||
|
| Use more than 1000 m above | ||||||
|
| sea level results in the following | ||||||
|
| reduction in output power: | ||||||
|
|
|
|
|
|
|
|
|
| Height(m) |
| 1000 | 1500 | 2000 | 2500 | 3000 |
|
|
|
|
|
|
|
|
|
|
| Output power |
| 100% | 95% | 90% | 85% | 80% |
|
|
|
|
|
|
|
|
|
|
13