♦Mechanically secure the cables with the strain relief clamps of the cable clamping unit.
♦Mount the connection cover of the cable clamping unit.
5.3.1ConnectionThe required dimensions can be found in the following table:
|
| PROTECT |
| PROTECT | PROTECT | ||
|
| 1.100 |
| 1.150* | 1.200* | ||
|
|
|
|
|
|
|
|
Max. current consumption |
| 46A |
| 68A | 91A | ||
(bypass) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Incoming mains | min. | 10 mm² |
| 16 mm² | 25 mm² | ||
cable (UPS input) | max. | 16 mm² |
| 35 mm² | 35 mm² | ||
|
| ||||||
|
|
|
|
|
|
|
|
Load connection | min. | 10 mm² |
| 16 mm² | 25 mm² | ||
(UPS output) | max. | 16 mm² |
| 35 mm² | 35 mm² | ||
|
| ||||||
|
|
|
|
|
|
|
|
Battery connection |
| Via enclosed |
| Min. 16 mm², Max. 35 | |||
|
| battery |
| mm² per terminal | |||
|
| connection |
| Battery connection cable | |||
|
| cable protect- |
| ||||
|
|
| is included with the | ||||
|
| ted against |
| ||||
|
|
| battery unit | ||||
|
| polarity |
| ||||
|
|
| Observe | ||||
|
| reversal |
| ||||
|
|
| |||||
|
|
|
| ||||
|
|
|
|
|
|
|
|
Mains fuse (UPS input) |
| 50A gl |
| 80A gl |
|
| 100A gl |
|
| When using line |
| safety switches, |
| observe | |
|
|
|
| ||||
|
| trigger characteristic: “D” |
|
|
| ||
|
| ||||||
Load fuse (recommended | Line safety switch “B” characteristic | ||||||
max.) |
| 16A |
| 20A |
|
| 25A |
|
|
|
| ||||
|
|
|
|
| |||
|
|
|
|
|
|
|
|
*To ensure a reliable strain relief, individual wires must be laid especially for connecting the 15 and 20 kVA UPS systems.
Recommended connection cable acc. to VDESpecially for 15 and 20 kVA: Special
or NYY or
Radox
30