Message / display | Cause | Solution |
|
|
|
Duration of the | Batteries not | Charge the batteries for |
emergency power | completely charged | at least the recharging |
supply shorter than | / batteries aged or | time acc. to chapter 2.3, |
setpoint. | faulty. | and check their capacity. |
|
| If the problem remains, |
|
| contact your dealer. |
|
|
|
“Line” LED and “Fault” | Make sure that no | |
LED light up, continuous | UPS internal | overload is present, the |
warning signal (error | overtemperature | UPS fans are not |
description no. 17). | detection | blocked and the ambient |
|
| temperature is in the |
|
| tolerance range. Wait for |
|
| 10 min. cooling down |
|
| phase, then switch on |
|
| again. |
|
|
|
Error description no. 19 | Correct | |
| Switch UPS on again, | |
| output | connect loads one after |
|
| the other again. |
|
|
|
“Fault” LED lights up, | Fault in DC circuit | Notify dealer! |
“Battery” LED flashes, | or battery system |
|
warning signal sounds | faulty. |
|
once per second (error |
|
|
description 21). |
|
|
|
|
|
“Fault” LED lights up, | Fault in the UPS. | Notify dealer! |
continuous warning |
|
|
signal. |
|
|
|
|
|
Further diagnoses can also be found in the table list in chapter 8.1.2.
If you cannot solve the problem that has occurred, stop the entire procedure, switch off the UPS and disconnect the UPS from the mains. Please contact our hotline in this case (see p. 4).
Please have the serial number of the unit as well as the purchase date at hand. The hotline will provide you with technical support and can inform you about further procedures once you have described the problem.
50