| Flash Codes | |
|
|
|
|
|
| LED | Fault Description | Troubleshooting Information |
|
| Status |
| ||
|
|
|
| |
|
|
|
|
|
| POWER | Module has power | Supply voltage is present at module terminals |
|
| (Green) |
| ||
|
|
|
| |
|
|
|
|
|
|
|
| 1. Compressor protector is open |
|
|
|
| * Check for high head pressure |
|
|
| Thermostat demand | * Check compressor supply voltage |
|
| TRIP | signal Y1 is present, | 2. Outdoor unit power disconnect is open |
|
| (Red) | but the compressor | 3. Compressor circuit breaker or fuse(s) is open |
|
|
| is not running | 4. Broken wire or connector is not making contact |
|
|
|
| 5. Low pressure switch open if present in system |
|
|
|
| 6. Compressor contactor has failed open |
|
|
|
|
|
|
|
|
| 1. Low refrigerant charge |
|
|
|
| 2. Evaporator blower is not running |
|
|
|
| * Check blower relay coil and contacts |
|
|
|
| * Check blower motor capacitor |
|
|
|
| * Check blower motor for failure or blockage |
|
|
|
| * Check evaporator blower wiring and connector |
|
|
|
| * Check indoor blower control board |
|
|
|
| * Check thermostat wiring for open circuit |
|
| ALERT | Long Run Time | 3. Evaporator coil is frozen |
|
| Compressor is | * Check for low suction pressure |
| |
| (Yellow) |
| ||
| running | * Check for excessively low thermostat setting |
| |
| Flash |
| ||
| extremely long run | * Check evaporator airflow (coil blockages or return air filter) |
| |
| Code 1 |
| ||
| cycles | * Check ductwork or registers for blockage |
| |
|
|
| ||
|
|
| 4. Faulty metering device |
|
|
|
| * Check TXV bulb installation (size, location, and contact) |
|
|
|
| * Check if TXV/fixed orifice is stuck closed or defective |
|
|
|
| 5. Condenser coil is dirty |
|
|
|
| 6. Liquid line restriction (filter drier blocked if present in system) |
|
|
|
| 7. Thermostat is malfunctioning |
|
|
|
| * Check thermostat |
|
|
|
| * Check thermostat installation (location, level) |
|
|
|
|
|
|
|
|
| 1. High head pressure |
|
|
|
| * Check high pressure switch if present in system |
|
|
| System | * Check if system is overcharged with refrigerant |
|
| ALERT | Pressure Trip | * Check for |
|
| Discharge or suction | 2. Condenser coil poor air circulation (dirty, blocked, damaged) |
| |
| (Yellow) |
| ||
| pressure | 3. Condenser fan is not running |
| |
| Flash |
| ||
| out of limits or | * Check fan capacitor |
| |
| Code 2 |
| ||
| compressor | * Check fan wiring and connectors |
| |
|
|
| ||
|
| overloaded | * Check fan motor for failure or blockage |
|
|
|
| 4. Return air duct has substantial leakage |
|
|
|
| 5. If low pressure switch present in system, check Flash Code 1 info |
|
|
|
|
|
|
|
|
|
|
|
|
|
| Table 9 |
Issue 1008 | Page 17 |