Allied Air Enterprises 4AC16LT Flash Codes, Fault Description, Troubleshooting Information, Trip

Models: 4AC16LT

1 22
Download 22 pages 9.31 Kb
Page 17
Image 17

 

 

 

Flash Codes

 

 

 

 

 

 

LED

Fault Description

Troubleshooting Information

 

 

Status

 

 

 

 

 

 

 

 

 

 

 

POWER

Module has power

Supply voltage is present at module terminals

 

 

(Green)

 

 

 

 

 

 

 

 

 

 

 

 

 

1. Compressor protector is open

 

 

 

 

* Check for high head pressure

 

 

 

Thermostat demand

* Check compressor supply voltage

 

 

TRIP

signal Y1 is present,

2. Outdoor unit power disconnect is open

 

 

(Red)

but the compressor

3. Compressor circuit breaker or fuse(s) is open

 

 

 

is not running

4. Broken wire or connector is not making contact

 

 

 

 

5. Low pressure switch open if present in system

 

 

 

 

6. Compressor contactor has failed open

 

 

 

 

 

 

 

 

 

1. Low refrigerant charge

 

 

 

 

2. Evaporator blower is not running

 

 

 

 

* Check blower relay coil and contacts

 

 

 

 

* Check blower motor capacitor

 

 

 

 

* Check blower motor for failure or blockage

 

 

 

 

* Check evaporator blower wiring and connector

 

 

 

 

* Check indoor blower control board

 

 

 

 

* Check thermostat wiring for open circuit

 

 

ALERT

Long Run Time

3. Evaporator coil is frozen

 

 

Compressor is

* Check for low suction pressure

 

 

(Yellow)

 

 

running

* Check for excessively low thermostat setting

 

 

Flash

 

 

extremely long run

* Check evaporator airflow (coil blockages or return air filter)

 

 

Code 1

 

 

cycles

* Check ductwork or registers for blockage

 

 

 

 

 

 

 

4. Faulty metering device

 

 

 

 

* Check TXV bulb installation (size, location, and contact)

 

 

 

 

* Check if TXV/fixed orifice is stuck closed or defective

 

 

 

 

5. Condenser coil is dirty

 

 

 

 

6. Liquid line restriction (filter drier blocked if present in system)

 

 

 

 

7. Thermostat is malfunctioning

 

 

 

 

* Check thermostat sub-base or wiring for short circuit

 

 

 

 

* Check thermostat installation (location, level)

 

 

 

 

 

 

 

 

 

1. High head pressure

 

 

 

 

* Check high pressure switch if present in system

 

 

 

System

* Check if system is overcharged with refrigerant

 

 

ALERT

Pressure Trip

* Check for non-condensable in system

 

 

Discharge or suction

2. Condenser coil poor air circulation (dirty, blocked, damaged)

 

 

(Yellow)

 

 

pressure

3. Condenser fan is not running

 

 

Flash

 

 

out of limits or

* Check fan capacitor

 

 

Code 2

 

 

compressor

* Check fan wiring and connectors

 

 

 

 

 

 

overloaded

* Check fan motor for failure or blockage

 

 

 

 

4. Return air duct has substantial leakage

 

 

 

 

5. If low pressure switch present in system, check Flash Code 1 info

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 9