|
| Miswired Module Troubleshooting | |
|
|
|
|
| Miswired Module Indication | Recommended Troubleshooting Action |
|
|
|
|
|
| Green LED is not on, | Determine if both R and C module terminals are connected. Verify voltage is present |
|
| at module's R and C terminals. Review 24VAC Power Wiring section on page 16 for |
| |
| module does not power up. |
| |
| R and C wiring. |
| |
|
|
| |
|
|
|
|
| Green LED intermittent, | Determine if R and Y terminals are wired in reverse. Verify module's R and C |
|
| module powers up only | terminals have a constant source. Review 24VAC Power Wiring section on page 16 |
|
| when compressor runs. | for R and C wiring. |
|
|
|
|
|
| TRIP LED is on but system | Verify Y terminal is connected to 24VAC at contactor coil. Verify voltage at contactor |
|
| and compressor check OK. | coils falls below 0.5VAC when off. |
|
|
|
|
|
| TRIP LED and ALERT LED | Verify R and C terminals are supplied with |
|
| flashing together. |
| |
|
|
| |
|
|
|
|
| ALERT Flash Code 3 | Verify Y terminal is connected to 24VAC at contactor coil. Verify voltage at contactor |
|
| (Compressor Short Cycling) |
| |
| coil falls below 0.5VAC when off. |
| |
| displayed incorrectly. |
| |
|
|
| |
|
|
|
|
| ALERT Flash Code 5, 6, or 7 | Check that compressor run and start wires are through module's current sensing |
|
| (Open Circuit, Open Start |
| |
| holes. Verify Y terminal is connected to 24VAC at contactor coil. Verify voltage at |
| |
| Circuit, or Open Run Circuit) |
| |
| contactor coil falls below 0.5VAC when off. |
| |
| displayed incorrectly. |
| |
|
|
| |
|
|
|
|
| ALERT Flash Code 6 |
|
|
| (Open Start Circuit) | Check that compressor run and start wires are routed through correct module |
|
| displayed for Code 7 |
| |
| sensing holes. |
| |
| (Open Run Circuit |
| |
|
|
| |
| or vice versa. |
|
|
|
|
|
|
| ALERT Flash Code 8 | Determine if module's Y terminal is connected. Verify Y terminal is connected to 24VAC at |
|
| contactor coil. Verify 24VAC is present across Y and C when thermostat demand signal is |
| |
| (Welded Contactor) |
| |
| present. If not, R and C are reverse wired. Verify voltage at contactor coil falls below |
| |
| displayed incorrectly. |
| |
| 0.5VAC when off. Review Thermostat Demand Wiring on page 16 for Y and C wiring. |
| |
|
|
| |
|
|
|
|
|
|
|
|
|
| Table 11 |
Issue 1008 | Page 19 |