Ball Type Service Valve

(Valve Open)

Use adjustable wrench. To open, rotate stem counterclockwise 1/4 turn (90°). To close, rotate stem clockwise 1/4 turn (90°).

Figure 11

Leak Testing

After the line set has been connected to the indoor and outdoor units, the line set connections and indoor unit must be checked for leaks.

WARNING

Fire, Explosion, and Personal Safety Hazard.

Failure to follow this warning could result in damage, personal injury, or death.

Never use oxygen to pressurize or purge refrigeration lines. Oxygen, when exposed to a spark or open flame, can cause damage by fire and/or an explosion, that could result in personal injury or death.

Using an Electronic Leak Detector

1.Connect the high pressure hose of the manifold gauge set to the suction valve service port. (Normally the high pressure hose is connected to the liquid line port; however, connecting it to the suction ports helps to protect the manifold gauge set from damage caused by high pressure.)

2.With both manifold valves closed, connect the cylin- der of R410A refrigerant. Open the valve on the R410A cylinder (vapor only).

3.Open the high pressure side of the manifold to allow R410A into the line set and indoor unit. Weigh in a trace amount of R410A. (A trace amount is a maxi- mum of 2 oz. of refrigerant or 3 lbs. pressure.) Close the valve on the R410A cylinder and the valve on the high pressure side of the manifold gauge set. Discon- nect the R410A cylinder.

4.Connect a cylinder of nitrogen with a pressure regulat- ing valve to the center port of the manifold gauge set.

When using high pressure gas such as nitrogen for this purpose, be sure to use a regulator that can control the pressure down to 1 or 2 psig.

5.Adjust nitrogen pressure to 150 psig. Open the valve on the high side of the manifold gauge set to pressur- ize the line set and the indoor coil.

6.After a short period of time, open a refrigerant port to make sure that an adequate amount of refrigerant has been added for detection (refrigerant requirements will vary with lengths). Check all joints for leaks. Purge nitrogen and R410A mixture. Correct any leaks and recheck.

Evacuation

Evacuating the system of noncondensables is critical for proper operation of the unit. Noncondensables are defined as any gas that will not condense under temperatures and pressures present during operation of an air conditioning system. Noncondensables and water vapor combine with refrigerant to produce substances that corrode copper piping and compressor parts.

WARNING

Do not use a compressor to evacuate a sys- tem. Avoid deep vacuum operation. Extremely low vacuums can cause internal arcing and compressor failure. Danger of equipment damage. Damage caused by deep vacuum operation will void warranty.

Use a thermocouple or thermistor electronic vacuum gauge that is calibrated in microns. Use an instrument that reads down to 50 microns.

1.Connect the manifold gauge set to the service valve ports as follows:

• Low pressure gauge to suction line service valve

• High pressure gauge to liquid line service valve

506467-01

Issue 1008

Page 10

Page 10
Image 10
Allied Air Enterprises 4AC16LT manual Ball Type Service Valve Valve Open, Leak Testing, Using an Electronic Leak Detector

4AC16LT specifications

The Allied Air Enterprises 4AC16LT is a highly efficient air conditioning unit designed to provide optimal cooling solutions for residential and light commercial applications. This model exemplifies the balance of innovative technology and user-friendly features, making it a popular choice for homeowners and contractors alike.

One of the standout characteristics of the 4AC16LT is its ENERGY STAR certification, which signifies its energy efficiency and eco-friendly operation. The unit is engineered to reduce energy consumption while delivering reliable performance, ultimately helping to lower electricity bills for consumers.

The 4AC16LT features a scroll compressor, a technology known for its durability and efficiency. This compressor design not only improves the overall cooling efficiency but also minimizes operational noise, providing a quiet and comfortable indoor environment. The unit's sound levels are notably reduced, making it ideal for residential settings where noise can be a significant concern.

In addition to its efficient compressor, the unit boasts a range of advanced technologies. The integrated smart diagnostic features allow technicians to quickly identify and troubleshoot issues, streamlining maintenance and reducing downtime. This is particularly beneficial for contractors, as it enhances service response times and customer satisfaction.

The 4AC16LT is also equipped with a durable cabinet design, which is resistant to rust and corrosion, ensuring longevity and reliability in various environmental conditions. The pre-painted steel casing not only enhances the unit’s durability but also adds an aesthetic appeal that blends well with most home exteriors.

Further enhancing its appeal, the unit utilizes environmentally friendly refrigerants that comply with current regulations. This commitment to sustainability demonstrates Allied Air Enterprises’ focus on innovation while caring for the environment.

Moreover, the model is designed with ease of installation in mind. The compact size and lightweight construction of the 4AC16LT facilitate straightforward installation, saving time and labor costs for technicians.

In summary, the Allied Air Enterprises 4AC16LT air conditioning unit is a top-tier choice that incorporates energy efficiency, advanced technology, and a user-friendly design. Its combination of quiet operation, robust features, and commitment to sustainability makes it an excellent investment for anyone seeking reliable indoor comfort.