Allied Air Enterprises A93DF, A95DF, 92G1DF, 95G1DF Installation on Non-Combustible Flooring Figure

Models: A95DF 95G1DF A93DF 92G1DF

1 48
Download 48 pages 31.8 Kb
Page 10
Image 10

WARNING

Improper installation of the furnace can result in personal injury or death. Combustion and flue products must never be allowed to enter the return air system or air in the living space. Use sheet metal screws and joint tape to seal return air system to furnace.

In platform installations with furnace return, the furnace should be sealed airtight to the return air plenum. A door must never be used as a portion of the return air duct system. The base must provide a stable support and an airtight seal to the furnace. Allow absolutely no sagging, cracks, gaps, etc.

For no reason should return and supply air duct systems ever be connected to or from other heating devices such as a fireplace or stove, etc. Fire, explosion, carbon monoxide poisoning, personal injury and/or property damage could result.

The unit may be installed three ways in downflow applica- tions: on non-combustible flooring, on combustible flooring using an additive base, or on a reverse-flow cooling coil cabinet. Do not drag the unit across the floor in the downflow position. Floor and furnace flange damage will result.

Refer to Figure 11 for clearances in downflow applica- tions.

Downflow Application Installation Clearances

Top

Left Side

Right Side

 

Bottom

 

 

Top

 

0

 

 

 

*Front

 

0

 

 

 

Back

 

0

 

 

 

Sides

 

0†

 

 

 

Vent

 

0

 

 

 

Floor

 

NC ‡

 

 

 

*Front clearance in alcove installation must be 24 in. (610 mm). Maintain a minimum of 24 in. (610 mm) for front service access. †Allow proper clearances to accommodate condensate trap.

‡The furnace may be installed on a combustible wood floor if an optional additive base is installed between the furnace and the combustible floor.

FIGURE 11

Installation on Non-Combustible Flooring (Figure 12)

1.Cut floor opening keeping in mind clearances listed on unit rating plate. Also keep in mind gas supply connections, electrical supply, flue and air intake connections and sufficient installation and servicing clearances. See Table 1 for correct floor opening size.

2.Flange warm air plenum and lower the plenum into the opening.

3.Set the unit over the plenum and seal the plenum to the unit.

4.Ensure that the seal is adequate.

NON−COMBUSTIBLE FLOOR OPENING SIZE

Cabinet Width

Front to Rear

Side to Side

 

 

 

 

in .

mm

in.

mm

 

 

 

 

 

 

B Cabinet (17.5")

19 − 3/4

502

16 − 5/8

422

 

 

 

 

 

C Cabinet (21")

19 − 3/4

502

20−1/8

511

 

 

 

 

 

NOTE: Floor opening dimensions listed are 1/4 inch (6 mm) larger than the unit opening. See dimension drawing on page 2.

TABLE 1

FURNACE

PROPERLY

 

SIZED FLOOR

SUPPLY AIR

OPENING

PLENUM

FIGURE 12

Installation on Combustible Flooring (Figure 13)

1.When unit is installed on a combustible floor, a downflow combustible flooring base must be installed between the furnace and the floor. The base must be ordered separately. See Table 2 for opening size to cut in floor.

CAUTION

The furnace and combustible flooring base shall not be installed directly on carpeting, tile, or other combustible material other than wood flooring.

Page 10 of 48

Issue 1109

506725-01

Page 10
Image 10
Allied Air Enterprises A93DF, A95DF Installation on Non-Combustible Flooring Figure, NON−COMBUSTIBLE Floor Opening Size