Testing for Proper Venting and Sufficient Combustion Air for Non-Direct Vent Applications

WARNING

CARBON MONOXIDE POISONING HAZARD

Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death.

The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation.

After the gas furnace has been started, the following test should be conducted to ensure proper venting and sufficient combustion air has been provided to the unit as well as to other gas fired appliances which are separately vented.

If this furnace replaces a Category I furnace which was commonly vented with another gas appliance, the size of the existing vent pipe for that gas appliance must be checked. Without the heat of the original furnace flue

6.Follow the lighting instruction to place the appliance being inspected into operation. Adjust thermostat so appliance will operate continuously.

7.Use the flame of a match or candle to test for spillage of flue gases at the draft hood relief opening after 5 minutes of main burner operation.

8.If improper venting is observed during any of the above tests, the venting system must be corrected or sufficient combustion/makeup air must be provided. The venting system should be resized to approach the minimum size as determined by using the appropriate tables in appendix G in the current standards of the National Fuel Gas Code ANSI-Z223.1/NPFA 54 in the U.S.A., and the appropriate Natural Gas and Propane appliances venting sizing tables in the current standard of the CSA- B149 Natural Gas and Propane Installation Codes in Canada.

9.After determining that each appliance remaining connected to the common venting system properly vents when tested as indicated in step 3, return doors, windows, exhaust fans, fireplace dampers and any other gas burning appliance to their previous condition of use.

products, the existing vent pipe is probably oversized for the single water heater or other appliance. The vent should be checked for proper draw with the remaining appliance.

The test should be conducted while all appliances (both in operation and those not in operation) are connected to the venting system being tested. If the venting system has been installed improperly, or if provisions have not been made for sufficient amounts of combustion air, corrections must be made as outlined in the previous section.

1.Seal any unused openings in the venting system.

2.Visually inspect the venting system for proper size and horizontal pitch. Determine there is no blockage or restriction, leakage, corrosion, or other deficiencies which could cause an unsafe condition.

3.To the extent that it is practical, close all building doors and windows and all doors between the space in which the appliances connected to the venting system are located and other spaces of the building.

4.Close fireplace dampers.

5.Turn on clothes dryers and any appliances not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan.

Page 38 of 48

Issue 1109

506725-01

Page 38
Image 38
Allied Air Enterprises A93DF, A95DF, 92G1DF, 95G1DF dimensions Carbon Monoxide Poisoning Hazard

A95DF, 95G1DF, A93DF, 92G1DF specifications

Allied Air Enterprises offers a range of high-efficiency commercial and residential heating and cooling systems, with models like the 92G1DF, A93DF, 95G1DF, and A95DF gaining popularity for their cutting-edge technology and advanced features. Each of these models stands out in performance, reliability, and energy efficiency, making them excellent choices for diverse applications.

The 92G1DF model features a multi-stage gas valve that enhances temperature regulation, allowing for more precise heating. With an impressive Annual Fuel Utilization Efficiency (AFUE) rating, this furnace efficiently utilizes fuel, resulting in lower energy costs and reduced emissions. Its compact design makes it suitable for installations in tight spaces, while the durable heat exchanger extends the unit’s lifespan.

In contrast, the A93DF is engineered for enhanced comfort and flexibility. This model incorporates a variable-speed blower motor, which adjusts air circulation according to the heating demands in the space. This feature not only maximizes comfort by providing consistent temperatures but also promotes energy savings by reducing unnecessary power consumption. Additionally, the A93DF includes advanced diagnostic capabilities that simplify troubleshooting and maintenance, making it a favorite among HVAC professionals.

The 95G1DF is another noteworthy model that combines versatile performance with exceptional efficiency. This furnace boasts an AFUE rating of up to 95%, making it one of the most efficient models in its class. Its innovative design includes a secondary heat exchanger that captures additional heat from exhaust gases, optimizing energy utilization. Furthermore, the 95G1DF is equipped with an advanced control system that allows homeowners to set specific comfort levels.

Lastly, the A95DF model takes efficiency to a new level. With features such as a modulating gas valve and a variable-speed blower, this unit seamlessly adapts to changing heating needs. The A95DF not only heats a space but also enhances air quality through advanced filtration options. Its whisper-quiet operation adds to user satisfaction, making it ideal for residential settings.

In summary, Allied Air Enterprises' models 92G1DF, A93DF, 95G1DF, and A95DF demonstrate a commitment to innovation and energy efficiency, with features designed to provide superior comfort and reliability. With their advanced technologies and high-performance characteristics, these models are positioned as top contenders in the heating and cooling marketplace, ensuring that customers can enjoy a comfortable environment year-round.