Details of Exhaust Piping Terminations for
NON−DIRECT VENT FIELD SUPPLIED WALL
TERMINATION EXTENDED
Exhaust pipe may be routed either horizontally through an outside wall or vertically through the roof. In attic or closet installations, vertical termination through the roof is preferred. Figures 34 through 37 show typical terminations.
1. | Exhaust piping must terminate straight out or up as |
| shown. The termination pipe must be sized as listed in |
| Table 8. The specified pipe size ensures proper velocity |
| required to move the exhaust gases away from the |
| building. |
2. | On field supplied terminations for side wall exit, exhaust |
| piping may extend a maximum of 12 inches (305 mm) |
| for 2” PVC and 20” (508 mm) for 3” (76 mm) PVC beyond |
| the outside wall. See Figure 35. |
3. | If exhaust piping must be run up a sidewall to position |
| above snow accumulation or other obstructions, piping |
| must be supported every 24” (610 mm) as shown in |
UNCONDITIONED
SPACE
6" (152mm) Max
*WALL SUPPORT
OUTSIDE WALL
FIELD−PROVIDED
REDUCER MAY BE
REQUIRED TO
ADAPT LARGER
VENT PIPE SIZE TO
TERMINATION
1/2" (13mm) FOAM
INSULATION IN
UNCONDITIONED SPACE (IF REQUIRED)
12" (305mm) MAX. for 2" (51mm) 20" (508mm) MAX. for 3" (76mm)
SIZE TER-
MINATION
PIPE PER
TABLE 8.
12" (305mm)
ABOVE GRADE OR AVERAGE SNOW ACCUMULATION
1/2" (13mm) FOAM INSULATION (IF REQUIRED)
Figure 36. When exhaust piping must be run up an |
outside wall, any reduction in exhaust pipe size must be |
done after the final elbow. |
NON−DIRECT VENT ROOF TERMINATION KIT
| (15F75 or 44J41) |
| SIZE TERMINATION |
12" (305mm) | PIPE PER TABLE 8. |
ABOVE AVE. |
|
SNOW |
|
ACCUMULATION | 1/2" (13mm) FOAM |
| INSULATION IF REQUIRED |
3" (76mm) OR
2" (51mm) PVCUNCONDITIONED
ATTIC SPACE
PROVIDE SUPPORT
FOR EXHAUST LINES
FIGURE 34
NON−DIRECT VENT FIELD SUPPLIED WALL TERMINATION | ||
| 12" (305mm) MAX. for 2" (51mm) | |
| 20" (508mm) MAX. for 3" (76mm) | |
1/2" (13mm) ARMAFLEX |
| |
INSULATION IN |
| |
UNCONDITIONED SPACE (IF REQUIRED) | 1/2" (13mm) | |
FIELD−PROVIDED | ARMAFLEX | |
INSULATION | ||
REDUCER MAY | (IF REQUIRED) | |
BE REQUIRED TO |
| |
ADAPT LARGER |
| |
VENT PIPE SIZE | PVC REDUCER | |
TO TERMINATION | 12" MIN. | |
SIZE TERMINATION | ||
(305mm) | ||
PIPE PER TABLE 8. | Above Grade or | |
| average snow | |
| accumulation |
FIGURE 35
*Use wall support every 24" (610). Use two supports if extension is greater than 24" but less than 48".
FIGURE 36
NON−DIRECT VENT APPLICATION
USING EXISTING CHIMNEY
SIZE TERMINATION |
|
|
| STRAIGHT−CUT OR | ||||||
PIPE PER TABLE 8. |
|
| ANGLE−CUT IN DIRECTION | |||||||
|
|
| OF ROOF SLOPE | |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| EXHAUST VENT | |||
|
|
|
|
|
|
| 1/2" (13mm) |
|
| |
Minimum 12" (305MM) |
|
| WEATHERPROOF |
|
| |||||
| INSULATION (IF REQUIRED) |
|
| |||||||
above chimney top |
|
|
| |||||||
|
|
|
|
|
| |||||
plate or average snow |
|
|
|
|
|
| ||||
SHOULDER OF FITTINGS |
| |||||||||
accumulation |
| PROVIDE SUPPORT |
| |||||||
|
|
|
|
| OF PIPE ON TOP PLATE |
| ||||
|
| SHEET |
|
|
|
|
|
|
| |
|
| METAL TOP |
|
|
|
|
|
|
| |
|
| PLATE |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
| INSULATE |
|
|
|
|
|
| |||
| TO FORM |
|
|
|
|
| EXTERIOR |
| ||
| SEAL |
|
|
|
|
| PORTION OF |
| ||
|
|
|
|
|
|
|
| CHIMNEY |
|
NOTE − Do not discharge exhaust gases directly into any chimney or vent stack. If ver- tical discharge through an existing unused chimney or stack is required, insert piping inside chimney until the pipe open end is above top of chimney and terminate as illus- trated. In any exterior portion of chimney, the exhaust vent must be insulated.
FIGURE 37
Issue 1109 | Page 25 of 48 |