Allied Air Enterprises 92G1DF, A95DF, A93DF NON−DIRECT Vent Application Using Existing Chimney

Models: A95DF 95G1DF A93DF 92G1DF

1 48
Download 48 pages 31.8 Kb
Page 25
Image 25

Details of Exhaust Piping Terminations for Non-Direct Vent Applications

NON−DIRECT VENT FIELD SUPPLIED WALL

TERMINATION EXTENDED

Exhaust pipe may be routed either horizontally through an outside wall or vertically through the roof. In attic or closet installations, vertical termination through the roof is preferred. Figures 34 through 37 show typical terminations.

1.

Exhaust piping must terminate straight out or up as

 

shown. The termination pipe must be sized as listed in

 

Table 8. The specified pipe size ensures proper velocity

 

required to move the exhaust gases away from the

 

building.

2.

On field supplied terminations for side wall exit, exhaust

 

piping may extend a maximum of 12 inches (305 mm)

 

for 2” PVC and 20” (508 mm) for 3” (76 mm) PVC beyond

 

the outside wall. See Figure 35.

3.

If exhaust piping must be run up a sidewall to position

 

above snow accumulation or other obstructions, piping

 

must be supported every 24” (610 mm) as shown in

UNCONDITIONED

SPACE

6" (152mm) Max

*WALL SUPPORT

OUTSIDE WALL

FIELD−PROVIDED

REDUCER MAY BE

REQUIRED TO

ADAPT LARGER

VENT PIPE SIZE TO

TERMINATION

1/2" (13mm) FOAM

INSULATION IN

UNCONDITIONED SPACE (IF REQUIRED)

12" (305mm) MAX. for 2" (51mm) 20" (508mm) MAX. for 3" (76mm)

SIZE TER-

MINATION

PIPE PER

TABLE 8.

12" (305mm)

ABOVE GRADE OR AVERAGE SNOW ACCUMULATION

1/2" (13mm) FOAM INSULATION (IF REQUIRED)

Figure 36. When exhaust piping must be run up an

outside wall, any reduction in exhaust pipe size must be

done after the final elbow.

NON−DIRECT VENT ROOF TERMINATION KIT

 

(15F75 or 44J41)

 

SIZE TERMINATION

12" (305mm)

PIPE PER TABLE 8.

ABOVE AVE.

 

SNOW

 

ACCUMULATION

1/2" (13mm) FOAM

 

INSULATION IF REQUIRED

3" (76mm) OR

2" (51mm) PVCUNCONDITIONED

ATTIC SPACE

PROVIDE SUPPORT

FOR EXHAUST LINES

FIGURE 34

NON−DIRECT VENT FIELD SUPPLIED WALL TERMINATION

 

12" (305mm) MAX. for 2" (51mm)

 

20" (508mm) MAX. for 3" (76mm)

1/2" (13mm) ARMAFLEX

 

INSULATION IN

 

UNCONDITIONED SPACE (IF REQUIRED)

1/2" (13mm)

FIELD−PROVIDED

ARMAFLEX

INSULATION

REDUCER MAY

(IF REQUIRED)

BE REQUIRED TO

 

ADAPT LARGER

 

VENT PIPE SIZE

PVC REDUCER

TO TERMINATION

12" MIN.

SIZE TERMINATION

(305mm)

PIPE PER TABLE 8.

Above Grade or

 

average snow

 

accumulation

FIGURE 35

*Use wall support every 24" (610). Use two supports if extension is greater than 24" but less than 48".

FIGURE 36

NON−DIRECT VENT APPLICATION

USING EXISTING CHIMNEY

SIZE TERMINATION

 

 

 

STRAIGHT−CUT OR

PIPE PER TABLE 8.

 

 

ANGLE−CUT IN DIRECTION

 

 

 

OF ROOF SLOPE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EXHAUST VENT

 

 

 

 

 

 

 

1/2" (13mm)

 

 

Minimum 12" (305MM)

 

 

WEATHERPROOF

 

 

 

INSULATION (IF REQUIRED)

 

 

above chimney top

 

 

 

 

 

 

 

 

 

plate or average snow

 

 

 

 

 

 

SHOULDER OF FITTINGS

 

accumulation

 

PROVIDE SUPPORT

 

 

 

 

 

 

OF PIPE ON TOP PLATE

 

 

 

SHEET

 

 

 

 

 

 

 

 

 

METAL TOP

 

 

 

 

 

 

 

 

 

PLATE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INSULATE

 

 

 

 

 

 

 

TO FORM

 

 

 

 

 

EXTERIOR

 

 

SEAL

 

 

 

 

 

PORTION OF

 

 

 

 

 

 

 

 

 

CHIMNEY

 

NOTE − Do not discharge exhaust gases directly into any chimney or vent stack. If ver- tical discharge through an existing unused chimney or stack is required, insert piping inside chimney until the pipe open end is above top of chimney and terminate as illus- trated. In any exterior portion of chimney, the exhaust vent must be insulated.

FIGURE 37

506725-01

Issue 1109

Page 25 of 48

Page 25
Image 25
Allied Air Enterprises 92G1DF NON−DIRECT Vent Application Using Existing Chimney, NON−DIRECT Vent Roof Termination KIT