HRV 1200SDD/1200SFD
HEAT RECOVERY VENTILATOR
PRODUCT
SPECIFICATIONS
AND ENGINEERING
INFORMATION
SUBMITTAL DATA
|
|
| 458 - | |
ALDES Model HRV 1200SFD or | ALDES HRV 1200SDD and | |||
1200SDD is a compact heat recov- | ||||
ery ventilator designed to exhaust |
| 1200SFD | ||
|
|
| ||
stale indoor air and supply fresh air | Heat Recovery Ventilator | |||
from outdoors. It is intended for | ||||
small commercial and institutional |
|
|
| |
applications, such as office build- |
|
|
| |
ings, classrooms, dormitories, res- |
|
|
| |
taurants, health clubs, etc. |
|
|
| |
It is a technically advanced con- |
|
|
| |
trolled mechanical ventilation sys- |
|
|
| |
tem to meet the requirements of | Optional Damper Defrost |
|
| |
modern, tightly built and highly in- | on Model 1200SDD |
|
| |
|
|
| ||
sulated buildings. It provides a |
|
|
| |
consistent supply of fresh air while | PART NO. 1200SFD / 28 130 |
| ||
lowering heating costs during the | 1200SDD / 28 131 |
| ||
|
|
| ||
winter by transferring heat from the |
|
|
| |
exhaust air to the fresh air stream. | The Model 1200 is available with | the cycle until temperatures rise | ||
During the summer it also reduces | ||||
two defrost options. | The Model | above 23 °F. The Model 1200SDD | ||
the load on the air conditioner by | ||||
1200SFD begins the defrost cycle | blocks outside air during defrost | |||
lowering the temperature of the | ||||
at temperatures below 23 °F | and draws indoor air through the | |||
fresh outdoor air. The system pro- | ||||
by shutting off the supply fan for 4- | supply (with the same temperature | |||
vides an economical solution for | ||||
1/2 minutes, then resumes normal | and defrost time schedule as the | |||
excessive indoor humidity, odors, | ||||
operation for 17 minutes, repeating | fan defrost system). | |||
stuffiness, and other indoor air pol- | ||||
|
|
| ||
lutants. |
| GENERAL FEATURES | ||
|
|
As the two air streams pass through | Thermally conductive aluminum heat exchange core, cross- | |
the HRV, they are separated by thin | flow design, easily removed for cleaning or service. | |
plates of aluminum in the core. The | Insulated 20 gauge powder coated galvanized steel cabinet. | |
air streams do not mix, so there is | Direct drive centrifugal forward curve blowers, | |
no recontamination of the fresh air | providing 600 to 1100 cfm. one in each air stream. | |
| ||
by stale air. Heat passes through | Two efficient three speed PSC double shafted motors 120 V, | |
the thermally conductive aluminum | 4 Amps each (8.1 Amps total on high speed), | |
1 ph. 1/4HP, 1625 RPM. Watts - total on high speed - 972. | ||
from the warmer air stream to the | ||
Washable filters, one in each air stream protect the core. Easy | ||
colder air stream, recovering most | ||
to access and clean. | ||
of the energy otherwise lost to the | Installation accessories and controls make installation simple. | |
| ||
outdoors. |
|