HRV 700SDD/700SFD
HEAT RECOVERY VENTILATOR
PRODUCT
SPECIFICATIONS
AND ENGINEERING
INFORMATION
SUBMITTAL DATA
|
| 496 - |
ALDES Model HRV 700SFD or | ALDES HRV 700SDD and | |
700SDD is a compact heat recov- | ||
stale indoor air and supply fresh air | 700SFD | |
ery ventilator designed to exhaust |
|
|
from outdoors. It is intended for | Heat Recovery Ventilator | |
small commercial and institutional |
|
|
applications, such as office build- |
|
|
ings, classrooms, dormitories, res- |
|
|
taurants, health clubs, etc. |
|
|
It is a technically advanced con- |
|
|
trolled mechanical ventilation sys- |
|
|
tem to meet the requirements of |
| Optional Damper Defrost |
modern, tightly built and highly in- |
| on Model 700 SDD |
|
| |
sulated buildings. It provides a |
|
|
consistent supply of fresh air while |
| PART NO. 700SFD / 28 105 |
lowering heating costs during the |
| 700SDD / 28 106 |
|
| |
winter by transferring heat from the |
|
|
exhaust air to the fresh air stream. | The Model 700 is available with two | temperatures rise above 23 °F. |
During the summer it also reduces | defrost options. The Model 700SFD | The Model 700SDD blocks out- |
the load on the air conditioner by | begins the defrost cycle at tempera- | side air during defrost and draws |
lowering the temperature of the | tures below 23 °F | indoor air through the supply (with |
fresh outdoor air. The system pro- | off the supply fan for | the same temperature and defrost |
vides an economical solution for | then resumes normal operation for | time schedule as the fan defrost |
excessive indoor humidity, odors, | 17 minutes, repeating the cycle until | system). |
stuffiness, and other indoor air pol- |
|
|
lutants. | GENERAL FEATURES | |
|
As the two air streams pass through | Thermally conductive aluminum heat exchange core, cross- | |
the HRV, they are separated by thin | flow design, easily removed for cleaning or service. | |
plates of aluminum in the core. The | Insulated 20 gauge powder coated galvanized steel cabinet. | |
air streams do not mix, so there is | Direct drive centrifugal forward curve blowers, | |
no recontamination of the fresh air | providing 400 to 650 cfm. one in each air stream. | |
Two efficient three speed PSC double shafted motors 120 V, | ||
by stale air. Heat passes through | ||
the thermally conductive aluminum | 2.75 Amps each (5.5 Amps total on high speed), | |
1 ph. 1/10 HP, 1625 RPM. Watts - total on high speed - 648. | ||
from the warmer air stream to the | ||
Washable filters, one in each air stream protect the core. Easy | ||
colder air stream, recovering most | ||
to access and clean. | ||
of the energy otherwise lost to the | Installation accessories and controls make installation simple. | |
outdoors. |
|