American Dryer Corp ID-170 installation manual Steam Damper System

Models: ID-170

1 55
Download 55 pages 5.2 Kb
Page 35
Image 35

b.The steam supply piping to the dryer must include a 12-inch (30.48 cm) rise along with a drip trap and check valve. This will prevent any condensate from entering the steam coil.

c.Flexible hoses or couplings must be used. The dryer vibrates slightly when it runs and this will cause the steam coil connections to crack if they are hard piped to the supply and return mains.

d.Shutoff valves for each dryer should be This will allow the dryer to be isolated maintenance work.

installed in the supply line, return line, and drip trap return line. from the supply main and the return main if the dryer needs

e.Install an inverted bucket steam trap and check valve at least 12-inches (30.48 cm) below the steam coil as close to the coil as possible.

1)An inverted bucket steam trap with a capacity of 1,400 lbs (635.02 kg) of condensate per hour @ 125 PSI (8.61 bars) is required for each dryer.

f.A 3/4” (19.05 mm) vacuum breaker should be installed. This will save energy and provide for the safety of the operator and maintenance personnel.

g.Water pockets in the supply line, caused by low points, will provide wet steam to the coil possibly causing steam coil damage. ALL horizontal runs of steam supply piping should be pitched 1/4-inch (6.35 mm) for every 1 foot (0.30 meters) back towards the steam supply header causing the condensate in the line to drain to the header. Install a bypass trap in any low point to eliminate wet steam.

STEAM DAMPER SYSTEM

31

Page 35
Image 35
American Dryer Corp ID-170 installation manual Steam Damper System