MLE-130 II (80 Kw Electric)

Reversing, 3ø

ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)

IMPORTANT: 208 VAC AND 230/240 VAC ARE NOT THE SAME. When ordering, specify exact voltage.

NOTES: A. When fuses are used they must be dual element, time delay, class RK1 or RK5 ONLY. Calculate/determine correct fuse value, by applying either local and/or National Electrical Codes to listed appliance amp draw data.

B.Circuit breakers are thermal-magnetic (industrial) type ONLY. For others, calculate/verify correct breaker size according to appliance amp draw rating and type of breaker used.

C.Circuit breakers for 3-phase (3ø) dryers must be 3-pole type.

OVEN SIZE

SERVICE

 

WIRE

APPROX.

PHASE

AMP DRAW

(Kw)

VOLTAGE

SERVICE

 

 

 

 

60 Hz

50 Hz

 

 

 

 

80

208

3

236

236

 

 

 

 

 

 

80

230/240

3

209

209

 

 

 

 

 

 

80

380-400

3/4

---

126

 

 

 

 

 

 

80

416

3/4

---

118

 

 

 

 

 

 

80

480

3/4

103

---

 

 

 

 

 

 

80

575

3

87

---

 

 

 

 

 

 

IMPORTANT: The dryer must be connected to the electric supply shown on the data label that is affixed to the left side panel/wall area behind the control door. In the case of 208 VAC or 230/240 VAC, the supply voltage must match the electric service specifications of the data label exactly.

WARNING: 208 VAC AND 230/240 VAC ARE NOT THE SAME. Any damage done to dryer components due to improper voltage connections will automatically VOID THE WARRANTY.

NOTE: ADC reserves the right to make changes in specifications at any time without notice or obligation.