Alarms and Events

5.2Displaying the Event Stack

Action

1.Press

2.Press

3.Press

4.Press

 

Description

and

Press the two keys simultaneously to get access

 

to the events stack

or

Scroll up or down through the event stack

 

(last message is "No (further) event").

 

Displays the time where the event happened.

 

Exits the event stack. If not operated the system

 

will exit the event stack automatically after 30

 

seconds.

5.3Possible Alarms

NOTICE!

Please note mains = utility

 

Alarms

Description

Action

 

 

 

 

1.

Peak current limiter active

Peak current limiter activated and

Check for blown fuses in

 

 

UPS switched to bypass

installation

 

 

operation.

 

 

 

System overload

 

 

 

 

 

2.

Bypass power supply fault

Fault in redundant PSU for

Call for assistance

 

 

bypass. UPS still 100% able to

 

 

 

operate in all modes.

 

 

 

 

 

3.

Delta current limiter active

Input current limiter activated and

Check for overload.

 

 

UPS switched to bypass

If message is repetitive -

 

 

operation

call for assistance

 

 

 

 

4.

Faulty fan

Blocked or faulty fan

Remove blocking or replace fan

 

 

 

 

5.

High DC warning

Switching off big output load

If alarm is repeated, reduce load

 

 

 

change

 

 

 

 

6.

High DC shutdown

UPS fault

Call for assistance

 

 

 

 

7.

Off-button activated

Off button or emergency power

 

 

shut down activated

 

 

 

 

 

8.

Synchronization error

UPS unable to synchronize with

Check if phase rotation of mains

 

 

input frequency

input voltage is correct. If OK, call

 

 

 

for assistance

 

 

 

 

9.

Inverter voltage error

Inverter average voltage outside

 

 

limits (normal message during

 

 

 

system start-up/switch-off

 

 

 

 

10. Parallel synchronization

Parallel UPS unable to

Check external parallel cables -

 

error

synchronize

call for assistance

 

 

 

 

990-4034

24

User Guide APC Silcon 10-40kW 208V/480V UPS

Page 24