| Alarms and Events | |
|
|
|
|
|
|
|
|
|
|
| 11. | Inverter current limiter active | Inverter overload | Reduce UPS output load |
|
|
|
|
|
| 12. | Overload. Load exceeding | UPS overload | Reduce UPS output load |
|
| 100% |
|
|
|
|
|
|
|
| 13. | Second power supply fault | UPS fault | Call for assistance |
|
|
| (only systems > 160kW) |
|
|
|
|
|
|
| 14. | Internal power supply fault | UPS fault. Only bypass operation | Call for assistance |
|
|
| possible |
|
|
|
|
|
|
| 15. | Battery MCCB is off | Battery MCCB/fuse not closed or | Close MCCB / insert new fuse. If |
|
|
| released | released again - |
|
|
|
| call for assistance. |
|
|
|
|
|
| 16. | **Q004 off** | Output switch position for UPS in | – |
|
|
| parallel |
|
|
|
|
|
|
| 17. | **Q003 off** | External bypass switch position | – |
|
|
|
|
|
| 18. | **Q002 off** | UPS output switch position | – |
|
|
|
|
|
| 19. | **Q001 off** | UPS input switch position | – |
|
|
|
|
|
| 20. | High temperature of isolation | Temperature of isolation input/ | Check fan, check for airflow |
|
| transformer | output transformer, too high | obstructions, check for overload |
|
|
|
|
|
| 21. | High temperature of main | Temperature of static input | Check fan, check for airflow |
|
| static switch | switch, too high | obstructions, check for overload |
|
|
|
|
|
| 22. | High temperature of bypass | Temperature of static bypass | Check fan, check for airflow |
|
| static switch | switch, too high | obstructions, check for overload |
|
|
|
|
|
| 23. | Main inverter failure | Temperature of main inverter, too | Check fan, check for airflow |
|
|
| high or inverter fuse blown | obstructions, check for overload, |
|
|
|
| check fuse |
|
|
|
|
|
| 24. | High temperature of delta | Temperature of delta inverter, too | Check fan, check for airflow |
|
| inverter | high | obstructions, check for overload |
|
|
|
|
|
| 25. | Low DC shutdown | Battery discharged to minimum | Ensure battery recharging |
|
|
| permissible level |
|
|
|
|
|
|
| 26. | Low DC warning | Battery nearly discharged | Save your data now |
|
|
|
|
|
| 27. | Mains momentarily outside | Short disturbances on mains | – |
|
| tolerance | supply (1 ms transients) |
|
|
|
|
|
|
| 28. | Mains outside tolerance | Mains input voltage R.M.S. value | – |
|
|
| outside tolerance |
|
|
|
|
|
|
| 29. | Mains frequency outside | Mains input frequency outside | – |
|
| tolerance | tolerance |
|
|
|
|
|
|
| 30. | Bypass momentarily outside | Short disturbances on bypass | – |
|
| tolerance | voltage |
|
|
|
|
|
|
| 31. | Bypass outside tolerance | Bypass input voltage outside | – |
|
|
| tolerance |
|
|
|
|
|
|
| 32. | Bypass frequency outside | Bypass input frequency outside | – |
|
| tolerance | tolerance |
|
|
|
|
|
|
| 33. | Output momentarily outside | Short disturbance on output | If message reappears - |
|
| tolerance | voltage (inrush current) | call for assistance |
|
|
|
|
|
|
|
|
|
User Guide APC Silcon | 25 |