American Power Conversion 10-40kW 208/480V manual System start-up now completed

Models: 10-40kW 208/480V

1 31
Download 31 pages 39.72 Kb
Page 8
Image 8

Stop/Start UPS and Operating the External Service Bypass

1.Check that the system has been in a stable environment for at least 12 hours enabling any condensation to evaporate prior to start-up.

2.Open front door(s)

3.Switch on utility power by closing Q001

If dual utility close bypass input switch Q010 See notice below.

Display shows

System type XXX

XXX kVA - XXX

4. Wait for approx. 10 seconds

5.

Press

on the keyboard

6.

Press

on the keyboard

7.Wait for approx. 1 second

8.Wait for approx. 1 minute

9.Close MCCBs in Battery Breaker Box or Battery Cabinet

10.Press the green ON button

11.Close the front door(s)

Stop charge DC capacitors : YES

Start charge DC capacitors : YES

Data stored

Start charge DC capacitors : YES

Insert fuse or close MCCB

**System OFF**

Normal operation load power XX%

System start-up now completed.

NOTICE!

One of the following display messages will appear by UPS start-up:

“STD”: Standard (single system)

“PAR”: Parallel System

“ECO”: Economy mode (single or parallel systems) (Last message has priority over the other two)

kVA size (XXX) and the voltage reads:

• XXXkVA - 208 (220 or 480 Volt)

990-4034

8

User Guide APC Silcon 10-40kW 208V/480V UPS

Page 8
Image 8
American Power Conversion 10-40kW 208/480V manual System start-up now completed