American Power Conversion 1609 user manual User Configurable Items, UPS settings

Models: 1609

1 14
Download 14 pages 6.63 Kb
Page 7
Image 7
User Configurable Items

User Configurable Items

User Configurable Items

UPS settings

Settings are adjusted through PowerChute software or optional Network Management Card.

Function

Factory

User Selectable

Description

Default

Choices

 

 

 

 

 

 

 

Automatic

Every 14 days

• Every 7 days

 

Set the interval at which the UPS will execute a

Self-Test

(336 hours)

(168 hours)

 

 

self-test.

 

 

• On start up only

 

 

 

• No self-test

 

 

 

 

 

 

 

UPS ID

UPS_IDEN

Up to eight characters

Uniquely identify the UPS (i.e. server name or

 

 

(alphanumeric)

 

location) for network management purposes.

 

 

 

 

 

 

Date of Last

Manufacture

mm/dd/yy

 

 

Reset this date when you replace the battery

Battery

Date

 

 

 

module.

Replacement

 

 

 

 

 

 

 

 

 

 

 

Minimum Capacity

0 percent

• 0%

60%

Specify the percentage to which batteries will

Before Return from

 

• 15%

75%

be charged following a low battery shutdown

Shutdown

 

• 30%

90%

before powering connected equipment.

 

 

• 45%

 

 

 

 

 

 

 

 

Voltage Sensitivity

High sensitivity

High sensitivity

 

The UPS detects and reacts to line voltage

 

 

Medium sensitivity

distortions by transferring to battery operation

 

 

to protect the connected equipment.

 

 

Low sensitivity

 

 

 

 

In situations of poor power quality, the UPS

 

 

 

 

 

 

 

 

 

 

may frequently transfer to battery operation. If

 

 

 

 

 

the connected equipment can operate normally

 

 

 

 

 

under such conditions, reduce the sensitivity

 

 

 

 

 

setting to conserve battery capacity and service

 

 

 

 

 

life.

 

 

 

 

 

 

Alarm Delay

Enable

• Enable

 

 

Mute ongoing alarms or disable all alarms

Control

 

• Mute

 

 

permanently.

 

 

• Disable

 

 

 

 

 

 

 

 

 

Shutdown Delay

90 seconds

• 0 s

360 s

Set the interval between the time when the UPS

 

 

• 90 s

450 s

receives a shutdown command and actual

 

 

• 180 s

540 s

shutdown.

 

 

• 270 s

630 s

 

 

 

 

 

 

 

8

Page 7
Image 7
American Power Conversion 1609 user manual User Configurable Items, UPS settings