American Power Conversion 1609 Storage, Maintenance, Transport, Replacing the Battery Module

Models: 1609

1 14
Download 14 pages 6.63 Kb
Page 9
Image 9
Storage, Maintenance, Transport

Storage, Maintenance, Transport

Storage, Maintenance, Transport

Storage

Store the UPS covered in a cool, dry location with the batteries fully charged.

At 5° to 86° F (–15° to 30° C), charge the UPS battery every six months.

At 86° to 113° F (30° to 45° C), charge the UPS battery every three months.

Replacing the Battery Module

This UPS has an easy-to-replace, hot-swappable battery module. Replacement is a safe procedure, isolated from electrical hazards. You may leave the UPS and connected equipment on during the replacement procedure.

Ensure battery replacement every 2-4 years.

Standard (40C) battery; Allen-Bradley catalog number: 1609-500SBAT.

High Temperature (50C) battery; Allen-Bradley catalog number: 1609-500HBAT.

Once the batteries are disconnected the connected equipment is not protected from power outages.

Refer to the appropriate replacement battery installation guide for battery module installation instructions. See your dealer or contact Rockwell Automation at 440-646-5800 for information on replacement battery modules.

Be sure to deliver the spent battery(s) to a recycling facility or ship it to the address specified in the replacement battery literature.

10

Page 9
Image 9
American Power Conversion 1609 user manual Storage, Maintenance, Transport, Replacing the Battery Module