5.0 Operation

5.2Test button functions 5.2.1 Line Voltage bar graph

When you press and release the rear-panel Test button, the LED front-panel indicators display a bar graph of the input line voltage connected to the UPS.

UPS version

 

 

 

 

 

 

Input Vac

 

 

 

 

 

 

 

 

 

 

 

 

120 Vac

104

110

116

 

 

122

 

 

128

 

100 Vac

90

96

102

 

 

108

 

 

114

 

220/230/240

 

210

221

232

 

 

245

 

 

257

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

This example shows the input line voltage is between 116 and 122 Vac (120 Vac UPS, see table for other versions).

If no indicators light and the UPS is plugged into a known working outlet, the line voltage is extremely low. Low voltage could be the result of an overloaded branch circuit, a misadjusted service pole transformer, or an intentional local service brownout. The UPS compensates for this problem using SmartBoost to increase the supplied load voltage.

If all five indicators light, the line voltage is high and should be checked by a qualified electrician.

Note: After approximately 4 seconds, the UPS beeps and replaces the Line Voltage

bar graph with the Output Voltage bar graph display (see Sec. 5.2.2).