Operating Modes
Shutdown Mode
In shutdown mode the UPS stops supplying power to the load, waiting for the return of utility power. If there is no utility power present, external devices (e.g., servers) connected to the computer interface can command the UPS to shut down. This is normally done to preserve battery capacity after the graceful shutdown of protected servers. The
Self-test
The UPS performs a
During the
If the UPS fails the
The loads are not affected by a failed test. Recharge the battery overnight and perform the
Low Battery
When the UPS is operating
Cold Start
When the UPS is off and there is no utility power, use the cold start feature to apply power to the loads from the UPS’s battery.
Note: Cold start is not a normal condition.
∙Press and hold the on/off/test button until the UPS emits a constant tone.
∙Release the on/off/test button during the tone to start the UPS.
Storage
Storage Conditions
Store the UPS covered and upright in a cool, dry location, with its battery fully charged. Before storing, charge the UPS for at least four hours.
Extended Storage
At
At +30 to +45 °C (+86 to +113 °F), charge the UPS’s battery every 3 months.
7 |
|