American Power Conversion AP9341 manual Link

Models: AP9341

1 24
Download 24 pages 5.76 Kb
Page 19
Image 19

Specifications

Sensors

Temperature (AP9335T)

Temperature accuracy

±3ºF (±2ºC), from 32 to

 

104ºF (0 to 40ºC)

Sensor operating

14 to 159ºF (–10 to 70ºC)

temperature

 

Maximum length of

50 ft (15.2 m)

cable

 

 

 

A-Link

 

 

 

Maximum length of

3280 ft (1000 m)

cable

 

 

 

Beacon

 

 

 

Maximum length of

330 ft (100 m)

cable

 

 

Temperature/Humidity (AP9335TH), optional

 

 

Temperature accuracy

±3ºF (±2ºC), from 32 to

 

104ºF (0 to 40ºC)

Humidity accuracy

±4% RH, 20 to 90% RH, at

 

77ºF (25ºC)

 

±8% RH, 30 to 80% RH,

 

from 59 to 95ºF (15 to 30ºC)

Sensor operating

14 to 159ºF (–10 to 70ºC)

temperature

 

User input

200 mS

response time

 

Maximum length of

50 ft (15.2 m)

cable

 

 

 

Temperature/Humidity Module

15